Sidewall Direct Venting - Lochinvar Shield SNR200-100 Installation And Service Manual

Lochinvar commercial water heater installation & service manual
Hide thumbs Also See for Shield SNR200-100:
Table of Contents

Advertisement

3

Sidewall direct venting

Vent/air termination – sidewall
Follow
WARNING
determining vent location to avoid
possibility of severe personal injury,
death, or substantial property damage.
A gas vent extending through an exterior
WARNING
wall shall not terminate adjacent to a wall
or below building extensions such as
eaves, parapets, balconies, or decks.
Failure to comply could result in severe
personal injury, death, or substantial
property damage.
WARNING Do not connect any other appliance to the
vent pipe or multiple water heaters to a
common vent pipe. Failure to comply
could result in severe personal injury,
death, or substantial property damage.
Installation must comply with local
NOTICE
requirements and with the National Fuel
Gas Code, ANSI Z223.1 for U.S.
installations or CSA B149.1 for Canadian
installations.
Determine location
Locate the vent/air terminations using the following
guidelines:
1. The total length of piping for vent or air must not exceed
the limits given in the General Venting Section on page 17
of this manual.
2.
You must consider the surroundings when terminating
the vent and air:
a.
Position the vent termination where vapors will
not damage nearby shrubs, plants or air
conditioning equipment or be objectionable.
b.
The flue products will form a noticeable plume as
they condense in cold air. Avoid areas where the
plume could obstruct window views.
c.
Prevailing
winds
condensate and water/ice buildup where flue
products impinge on building surfaces or plants.
d. Avoid possibility of accidental contact of flue
products with people or pets.
e.
Do not locate the terminations where wind eddies
could affect performance or cause recirculation,
such as inside building corners, near adjacent
buildings or surfaces, window wells, stairwells,
alcoves, courtyards, or other recessed areas.
Sidewall vent and air inlet terminations
WARNING
must terminate in the same pressure
zone.
18
instructions
below
when
could
cause
freezing
TM
f.
Do not terminate above any door or window.
Condensate can freeze, causing ice formations.
g.
Locate or guard vent to prevent condensate damage
to exterior finishes.
Figure 3-1A Sidewall Termination of Air and Vent
FROM BOILER
VENT PIPE
CONNECTION
Table 3A Sidewall Vent Kits
Model
SNR150-100 -- SNR200-100
SNA285-125 -- SNA500-125
If using the alternate sidewall termination:
3. The air piping must terminate in a down-turned elbow as
shown in FIG. 3-1B. This arrangement avoids recirculation
of flue products into the combustion air stream.
4. The vent piping must terminate in an elbow pointed
outward or away from the air inlet, as shown in FIG. 3-1B.
Do not exceed the maximum lengths of the
WARNING
outside vent piping shown in FIG. 3-1B.
Excessive length exposed to the outside could
cause freezing of condensate in the vent pipe,
resulting in potential water heater shutdown.
Figure 3-1B Alternate Sidewall Termination of Air and
Vent w/Field Supplied Fittings
of
Installation & Service Manual
TO BOILER
INTAKE AIR
CONNECTION
VENT / AIR
TERMINATION
GRADE OR
SNOW LINE
Kit Number Vent Size
KIT30045
3 inch vent
KIT30046
4 inch vent
12"
MIN
TO
OVER-
HANG
12"
MIN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents