Gas Connections; Gas Connections Connecting Gas Supply Piping - Lochinvar 151 - 801 Operation Manual

Armor outdoor armor water heater
Hide thumbs Also See for 151 - 801:
Table of Contents

Advertisement

4

Gas connections

Connecting gas supply piping
1. Remove the top access panel and refer to FIG.'s 4-1 thru 4-4
to pipe gas to the water heater.
a.
Install ground joint union for servicing, when
required.
b.
On Models 151 - 400 install a manual shutoff valve in
the gas supply piping outside water heater jacket when
required by local codes or utility requirements.
2. Install sediment trap / drip leg.
Figure 4-1 Gas Supply Piping - Models 151 - 200
UNION
GAS SUPPLY
DRIP LEG
MANUAL
SHUT OFF
VALVE
(FIELD SUPPLIED)
Figure 4-2 Gas Supply Piping - Models 286 - 400
UNION
GAS SUPPLY
SEDIMENT TRAP /
DRIP LEG
MANUAL
SHUTOFF VALVE
(FIELD SUPPLIED)
Outdoor Armor Water Heater
Figure 4-3 Gas Supply Piping - Model 501
GAS SUPPLY
SEDIMENT TRAP/
DRIP LEG
Figure 4-4 Gas Supply Piping - Models 601 - 801
MANUAL SHUTOFF VALVE
(FACTORY SUPPLIED)
3. Support piping with hangers, not by the water heater or its
IMG00290
accessories.
WARNING
4. Purge all air from the gas supply piping.
5. Before placing the water heater in operation, check the
water heater and its gas connection for leaks.
a.
The appliance must be disconnected from the gas
supply piping system during any pressure testing of
that system at a test pressure in excess of 1/2 PSIG
(3.5 kPa).
b. The appliance must be isolated from the gas supply
piping system by closing a manual shutoff valve
during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 PSIG
(3.5 kPa).
IMG00397
c.
The appliance and its gas connection must be leak
tested before placing it in operation.
Installation & Operation Manual
MANUAL
SHUTOFF VALVE
(FACTORY SUPPLIED)
GAS SUPPLY
SEDIMENT TRAP/
DRIP LEG
The gas valve and blower will not support
the weight of the piping. Do not attempt
to support the weight of the piping with
the water heater or its accessories. Failure
to comply could result in severe personal
injury, death, or substantial property
damage.
UNION
(FACTORY INSTALLED)
IMG00398
IMG00296
21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents