13
Troubleshooting

Gas valve adjustment procedure

If adjustment of the gas valve is deemed necessary, use the
following procedures: (Note:
model specific.)
Models SNR150-100 -- SNA285-125
Locate the throttle adjustment screw on the side of the
venturi valve (FIG. 13-2). Using a screwdriver, turn the screw
a 1/4 turn clockwise to decrease CO
counterclockwise to increase CO
one adjustment on the valve, follow the Combustion Analysis
Procedure on page 68 of this manual to measure the
combustion.
If combustion is still not within the specified range, repeat
the procedure. This procedure SHOULD NOT be performed
more than four (4) times. If after four (4) adjustments and
the combustion is still not within the specified range, revisit
the possible causes in Table 13F on page 68 or replace the gas
valve.
Figure 13-2 Gas Valve Adjustment: Models
SNR150-100 -- SNA285-125
THROTTLE
ADJUSTMENT
SCREW
Model SNA400-125
Locate the throttle adjustment screw on the top of the gas
valve, see FIG. 13-3. Using a screwdriver, turn the screw 1/8
turn counterclockwise to increase CO
clockwise to decrease CO
2
the valve, follow the Combustion Analysis Procedure on page
68 of this manual to measure the combustion.
If combustion is still not within the specified range, repeat the
procedure. This procedure SHOULD NOT be performed
more than four (4) times. If after four (4) adjustments and
the combustion is still not within the specified range, revisit
the possible causes in Table 13F on page 68 or replace the gas
valve.
(continued)
The procedures below are
levels or a 1/4 turn
2
levels. After performing
2
levels or 1/8 turn
2
levels. After one adjustment on
Installation & Service Manual
TM
Figure 13-3 Gas Valve Adjustment: Model SNA400-125
THROTTLE
ADJUSTMENT
SCREW
Model SNA500-125
Locate the throttle adjustment screw on top of the gas valve, see
FIG. 13-4. Using a screwdriver, turn the screw a 1/4 turn
counterclockwise to increase CO
to decrease CO
levels. After one adjustment on the valve,
2
follow the Combustion Analysis Procedure on page 68 of this
manual to measure the combustion.
If combustion is still not within the specified range, repeat the
procedure. This procedure SHOULD NOT be performed more
than four (4) times. If after four (4) adjustments and the
combustion is still not within the specified range, revisit the
possible causes in Table 13F on page 68 or replace the gas valve.
Figure 13-4 Gas Valve Adjustment: Model SNA500-125
THROTTLE
ADJUSTMENT
SCREW
levels or a 1/4 turn clockwise
2
69