Gas Pressure; Gas Valve Replacement - Lochinvar Shield SNR200-100 Installation And Service Manual

Lochinvar commercial water heater installation & service manual
Hide thumbs Also See for Shield SNR200-100:
Table of Contents

Advertisement

7
Gas connections
17. Check burner performance by cycling the system while
you observe burner response. The burner should ignite
promptly. Flame pattern should be stable. Turn system
off and allow burner to cool, then cycle burner again to
ensure proper ignition and flame characteristics.
Figure 7-4 Inlet Gas Supply Check - Models SNR150/100
-- SNA285-125
LOOSEN THE SET SCREW ONE (1) FULL TURN AND
PLACE THE MANOMETER TUBING OVER THE
PRESSURE TAP
Figure 7-5 Inlet Gas Supply Check - Model SNA400/125
LOOSEN THE SET SCREW ONE (1) FULL TURN AND
PLACE THE MANOMETER TUBING OVER THE
PRESSURE TAP
Figure 7-6 Inlet Gas Supply Check - Model SNA500/125
LOOSEN THE SET SCREW ONE (1) FULL TURN AND
PLACE THE MANOMETER TUBING OVER THE
PRESSURE TAP
38

Gas pressure

The gas pressure must remain between 4 inches w.c. (natural),
8 inches w.c. (LP) minimum and 14 inches w.c. (natural and
LP) maximum during stand-by (static) mode and while in
operating (dynamic) mode. If an in-line regulator is used, it
must be a minimum of 10 feet from the Shield water heater.
It is very important that the gas line is properly purged by the
gas supplier or utility company. Failure to properly purge the
lines or improper line sizing, will result in ignition failure.
The problem is especially noticeable in NEW LP installations
and also in empty tank situations. This can also occur when a
utility company shuts off service to an area to provide
maintenance to their lines.

Gas valve replacement

The gas valve MUST NOT be replaced with a conventional gas
valve under any circumstances.
feature, this gas valve has a flanged connection to the venturi
and blower.
DETAIL
DETAIL
DETAIL
Installation & Service Manual
TM
Failure to follow all precautions could
WARNING
result in fire, explosion, or death!
DO NOT adjust or attempt to measure gas
WARNING
valve outlet pressure. The gas valve is
factory-set for the correct outlet pressure.
This setting is suitable for natural gas and
propane (when configured for LP),
requiring
Attempting to alter or measure the gas
valve outlet pressure could result in
damage to the valve, causing potential
severe
personal
substantial property damage.
As an additional safety
no
field
adjustment.
injury,
death,
or