IMPORTANT INFORMATION These instructions must be read and understood before installing, commissioning, operating or maintaining the equipment.
Technical specifications 1.1 Floor load Allow for the indirect water heaters weight and the maximum floor load; refer to the table (1.5 "General specifications"). 1.2 Working clearance For access to the indirect water heater, it is recommended that the following clearances are observed: around the anode connection: 100 cm.
Installation Note These products can be installed as vented and unvented. This manual only discusses unvented installations. For information about vented installations please contact your supplier. 2.1 Installation diagram The figures below show the installation diagrams. These diagrams are referred to in the sections describing the actual connection procedure.
Page 12
3. Fit a non-return valve (5) and an expansion vessel (16). 4. Fit an expansion valve (15) and connect the overflow side to an open waste water pipe. 2.2.2 Hot Water side See (B) in the installation diagram (2.1 "Installation diagram"). Note Insulating long hot water pipes prevents unnecessary energy loss.
Filling and draining Note These products can be installed as vented and unvented. This manual only discusses unvented installations. For information about vented installations please contact your supplier. Installation Diagram Legend 1. pressure relief valve (mandatory if mains water pressure is too high) 3.
3.2 Draining 1. Close the stop valve (4) between the cold water head tank and the cold water inlet (A). 2. Open the drain valve (9). 3. Bleed the water heater (or installation) so that it drains completely. Installation, Commissioning, User & Maintenance Instructions...
Maintenance Warning Maintenance may only be carried out by a competent person. At each service, the indirect water heater undergoes maintenance on water side. The maintenance must be carried out in the following order. 1. Preparation for maintenance 2. Water-side maintenance 3.
Page 16
4.2.2 Checking anodes Anodes ensure the protection of the tank by sacrificing themselves. Insufficient anode material may lead to poor protection and, hence, leakage of the tank. 1. Loosen the anodes one by one. 2. Check the diameter of each anode in different places. The diameter must be at least 60% of the original diameter.
Warranty Contact Lochinvar Ltd. or got to www.lochinvar.ltd.uk for the current warranty terms and conditions. 0312751_SIVS_100-220_UK_V4.1, 2022-06-27...