Gas Valve Adjustment Procedure - Lochinvar ARMOR 151 - 801 Service Manual

Lochinvar water heater user manual
Table of Contents

Advertisement

If adjustment of the gas valve is deemed necessary, use the
following procedures: (Note: The procedures in this section
are model specific.)
Locate the throttle adjustment screw on the side of the venturi
valve (FIG. 3-2). Using a screwdriver, turn the screw a 1/4
turn clockwise to decrease CO
counterclockwise to increase CO
one adjustment on the valve, follow the Combustion Analysis
Procedure on page 36 of this manual to measure the
combustion.
If combustion is still not within the specified range, repeat the
procedure. This procedure SHOULD NOT be performed
more than four (4) times. If after four (4) adjustments and
the combustion is still not within the specified range, revisit
the possible causes in Table 3H on page 36 or replace the gas
valve.
Figure 3-2
levels or a 1/4 turn
2
levels. After performing
2
Locate the throttle adjustment screw on the top of the gas
valve, see FIG. 3-3. Using a screwdriver, turn the screw 1/8
turn counterclockwise to increase CO
clockwise to decrease CO
2
the valve, follow the Combustion Analysis Procedure on page
36 of this manual to measure the combustion.
If combustion is still not within the specified range, repeat the
procedure. This procedure SHOULD NOT be performed
more than four (4) times. If after four (4) adjustments and
the combustion is still not within the specified range, revisit
the possible causes in Table 3H on page 36 or replace the gas
valve.
Figure 3-3
THROTTLE ADJUSTMENT
SCREW
Service Manual
levels or 1/8 turn
2
levels. After one adjustment on
37

Hide quick links: