Boiler Water Temperature Sensor - Viessmann Vitodens 050-W Installation And Service Instructions Manual

Wall mounted gas condensing boiler for natural gas and lpg
Table of Contents

Advertisement

Repairs
(cont.)

Boiler water temperature sensor

A
20
10
8
6
4
2
1
0.8
0.6
0.4
10 30 50 70 90 110
Temperature in °C
Sensor type: NTC 10 kΩ
1. Pull the leads from boiler water tem-
perature sensor A and check the
resistance.
2. Check the sensor resistance and
compare it with the curve.
3. In the case of severe deviation, drain
the boiler on the heating water side
and replace the sensor.
Danger
The boiler water temperature
sensor is immersed in heating
water (risk of scalding).
Drain the boiler before replac-
ing the sensor.
Troubleshooting
45

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents