Viessmann Vitodens 050-W Installation And Service Instructions Manual page 46

Wall mounted gas condensing boiler for natural gas and lpg
Table of Contents

Advertisement

Troubleshooting
Repairs
(cont.)
Checking the temperature limiter
46
Check the temperature limiter if the
burner control unit cannot be reset after
a fault shutdown, although the boiler
water temperature is below approx.
A
95 °C.
1. Pull the leads from temperature lim-
iter A.
2. Check the continuity of the tempera-
ture limiter with a multimeter.
3. Remove the faulty temperature lim-
iter.
4. Install a new temperature limiter.
5. Reset by pressing "Reset" on the
control unit to (see page 42).