5 Commissioning (functional checks)

5.1

Pilot ignition check

Ignite the pilot light as described in the user manual
Check if the pilot burner stays alight
Extinguish the pilot burner
5.2

Check functional burner and pilot burner

The appliance is preset to give the correct heat input. No further adjustment is necessary.
Always check the inlet pressure and burner pressure:
Turn off the gas valve on the appliance
Turn the inlet pressure test point C and apply the manometer
Check if the measured pressure is the same as the prescribed pressure
Perform this measuring when the appliance burns on full capacity and when only the
pilot ignition burns
When the pressure is too low, check if the gas pipes are made of material with the
right diameter
When the pressure is too high (more than 5 mBar overpressure) you can't install the
appliance and you should contact your gas company
Always check the burner pressure when the functional pressure is right
Open the burner pressure test point D
The pressure should match the described pressure. If this is not the case, then
contact the supplier
Note: After checking the burner pressure, the inlet pressure test point has to be shut and
checked for gas-tightness.
Fig. 23: Gas control Block
A. Governor
B. Adjusting screw pilot flame
C. Inlet pressure test point
D. Burner pressure test point