2. Summary of Programmed System Parameters

Parameter
Amb Tmp Alm
Ambient temperature alarm level
Volts Hi
System output volts high threshold
Volts Low
System Output volts low threshold
System:
Select system duty type
No. of SMRs
Set number of SMRs in the system
Num Batteries
Number of Battery strings installed
FS Batt I
Battery current transducer full scale rating
CSU #
CSU Access code (up to 7 digits)
Date / Time
Current system date and time
AC 1-ph Menu
1ph ACV Hi
AC supply high voltage alarm
1ph ACV Lo
AC supply low voltage alarm
1ph ACF Hi
Frequency high alarm
1ph ACF Lo
Frequency low alarm
1ph ACI FS
AC supply current transducer full scale rating
AC 3-ph Menu
3ph ACV Hi
AC supply high voltage alarm
3ph ACV Lo
AC supply low voltage alarm
3ph ACF Hi
Frequency high alarm
3ph ACF Lo
Frequency low alarm
3ph ACI FS
AC supply current transducer full scale rating
Battery Monitor Menu
Bat Config
Battery Monoblock size x number
(see BCM section of manual for more detail)
BCM Batteries
Number of battery banks to be monitored
Vhi Cell
Cell high voltage alarm
Vlow Cell
Cell low voltage alarm
+dVc Cell
Cell positive deviation alarm
-dVc Cell
Cell negative deviation alarm
Site Monitor Menu
SMR Float
Operating float voltage
SMR Equalise
Operating equalisation voltage
SMR V High
SMR voltage high alarm
158-1872-01
Description
Base (System) Menu
Auxiliary Units Submenu
(After enabling AC 1-ph Monitor)
(After enabling 3-ph AC Monitor)
(After enabling Battery Monitor)
If included in the system refer to Site Monitor documentation.
SMR Menu
3)
UPS/Standby
10-30000A
0-9999999
configurat'ns
2)
3)
2
Rectifier Technologies
Range
Default
Value
30-99°C
55°C
26-33V
28.7V
20-27V
22.5V
UPS
0-225
1
1)
1-4
1
100A
0000000
220-315V
260V
140-270V
200V
50-65Hz
55Hz
40-60Hz
45Hz
10-500A
100A
220-315V
260V
140-270V
200V
50-65Hz
55Hz
40-60Hz
45Hz
10-500A
100A
Various
12 cells
1-4
1
2.0-16.0V
2.5V
1.0-12.0V
1.8V
5-99%
10%
5-99%
10%
27.5V
28.5V
26-32.5V
28.0V
Actual
Value