Battery Cell Lead Connection To The Bcm Board - Rectifier RT9- 24V Installation, Operation And Technical Manual

Rack power system
Table of Contents

Advertisement

Installation, Operation and Technical Manual
Rectifier Technologies

4.9.6 Battery Cell Lead Connection to the BCM board

The battery cell voltage sensing leads are terminated with 13 way female (Weco 5.0mm
pitch) screw terminals. This plugs onto the connectors on the BCM board. How the cell
voltage sense leads connect to the BCM board depends on the battery configuration. The
following figures show the connection between the battery to the BCM board for different
configurations of the battery. If more than 2 batteries are used a particular configuration,
simply repeat the connection method for batteries 3 and 4.
Figure 4.11 BCM connections to a 48V (24 cell) battery bank.
158-1872-01
35
19-Feb-14

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mcsu-4

Table of Contents