Site Monitor Settings - Rectifier RT9- 24V Installation, Operation And Technical Manual

Rack power system
Table of Contents

Advertisement

Installation, Operation and Technical Manual

4.8.5 Site Monitor Settings

Please observe following guidelines:
1. Label – name of monitored input, up to 8 characters. Leave blank for not used channels.
2. Hi T-hold – thresholds of analog channels to generate warning/alarm/output control. When set to zero the
threshold is disabled, adjustable up to 999.9
3. Lo T-hold – thresholds of analog channels to generate warning/alarm/output control. When set to zero the
threshold is disabled, adjustable up to 500.0
4. Scale – value of measured parameter corresponding to 4.00V of input signal. Adjustable up to 999.9
5. Unit – a symbol of measured parameter.
6. O1-O4 – mark to assign an output relay to an input. More than one input can be assigned to an output.
7.
Al – mark to generate Site Monitor alarm when input is active.
1)
Step of adjustment from WinCSU-2 is 0.1 units, from the Front Panel 1 unit.
Settings of Site Monitor in this system at the time of commissioning.
Input
Label
An 1
An 2
An 3
An 4
An 5
An 6
An 7
An 8
Dig 1
Dig 2
Dig 3
Dig 4
Dig 5
Dig 6
Dig 7
Dig 8
Dig 9
Dig 10
Dig 11
Dig 12
158-1872-01
1)
input units.
1)
input units.
O1
O2
O3
O4
Al
31
Hi T-hold
Lo T-hold
Mark for normally closed input
Rectifier Technologies
1)
.
Scale
Unit
Notes
19-Feb-14