DHW cylinder and heating water buffer cylinder
G Shut-off valve
H Flow regulating valve
(Recommendation: We recommend installation and adjustment
of the max. water flow rate in accordance with the 10-minute peak
output of the DHW cylinder)
K Pressure gauge connection
L Non-return valve
The safety valve must be installed.
4
*5
According to DIN 1988-2, a drinking water filter should be installed in systems with metal pipework. In line with DIN 1988, when using plastic
pipes Viessmann also recommends the installation of a drinking water filter to prevent contaminants entering the DHW system.
VIESMANN
58
(cont.)
M Drain
N Cold water
O Drinking water filter
*5
P Pressure reducer to DIN 1988-2, Dec. 1988 issue
R Non-return valve/pipe separator
S Diaphragm expansion vessel, suitable for DHW
Recommendation: Install the safety valve higher than the top edge of
the cylinder. This protects the valve against contamination, scaling and
high temperatures. The DHW cylinder must not be drained when work-
ing on the safety valve.
VITOLIGNO 200-S