1U Battery Pack Specifications; Lead Acid Battery Module Specifications; Lithium-Ion Battery Module Specifications - HP R12000 User Manual

Directflow ups
Hide thumbs Also See for R12000:
Table of Contents

Advertisement

1U battery pack specifications

Parameter
Height
Depth
Depth with cabling
Width
Weight
Battery module type
3U battery pack specifications
Parameter
Height
Depth
Depth with cabling
Width
Weight
Battery module type

Lead acid battery module specifications

Feature
Type
Weight
Backup life
Voltage
Charging

Lithium-ion battery module specifications

Feature
Type
Weight
Backup life
Voltage
Value
4.2 cm (1.65 in)
93.73 cm (36.9 in)
93.73 cm (36.9 in)
48.0 cm (18.90 in)
12 kg (26.5 lb)
Lithium-ion
Value
13.000 cm (5.118 in)
82.842 cm (32.615 in)
89.242 cm (35.135 in)
48.260 cm (19.000 in)
100 kg (220 lb)
Lead acid
Specification
Maintenance-free, sealed, valve regulated lead acid
batteries
20 kg (44 lb)
>1 minute of backup support for a 3-year minimum float
service life at 30°C (86°F)
>40 seconds of backup support after a 3-year minimum
float service life at 30°C (86°F)
Battery string voltage of 108 V
Complete charge in no more than 24 hours; partial charge in
approximately 3 hours to reach 80 percent capacity at
default nominal utility voltage and no load
Specification
Maintenance-free, sealed, lithium-ion batteries
1.4 kg (3.1 lb)
Up to 300 seconds (5 minutes) with full load and two packs
operating in parallel
Single battery string voltage of 43.2 V. The 1UBP unit is
345.6 V.
Specifications 113

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R18000

Table of Contents