WARNING:
Connect the power unit to a grounded utility power outlet.

Connecting devices

CAUTION:
drawn by this type of printer can overload the UPS.
CAUTION:
Before connecting load devices to the UPS, verify the following:
The ratings of the devices that will be connected do not exceed the UPS capacity, which will overload
the UPS
If the equipment rating is listed in amps, multiply the number of amps by the selected output voltage to
determine the VA.
The load devices are linear/PFC loads
After verification, connect the device power cords to the UPS output receptacles.

Starting power to the load

Start power to the load by placing the UPS in AC mode.
IMPORTANT:

Continuing the installation of components

HP DirectFlow Battery Packs and the HP DirectFlow UPS Management Module card can be installed for
extended run-time and advanced battery management. To install these components, see the following
instructions:
Installing battery packs (on page 33)
Installing the Management Module card (on page 57)
For instructions about testing the REPO port function, see "Verifying the REPO port connection (on page 79)."

Installing the Management Module card

The HP DirectFlow UPS Management Module web interface allows remote monitoring and control of the HP
DirectFlow Power Unit, HP DirectFlow UPS Management Module card, and any HP DirectFlow Battery Packs
installed in the configuration. Power usage information is accessed through the network connector located on
To prevent injury from electric shock or damage to the equipment:
Plug the input line cord into a grounded (earthed) electrical outlet that is installed near the
equipment and is easily accessible.
Do not disable the grounding plug on the input line cord. The grounding plug is an important
safety feature.
Do not use extension cords.
Do not plug laser printers into the UPS output receptacles. The instantaneous current
The DirectFlow UPS is intended to supply three-phase linear/PFC loads only.
AC power must be available the first time the UPS is started.
Installation 57