[P12 error]
<Only for 4-way air discharge cassette type models>
Turn off the power.
Are not there connections errors or
disconnection on connectors CN333 and CN334
of indoor unit P.C. board (MCC-1402)?
Remove connectors CN333 and
CN334 of indoor unit P.C. board
(MCC-1402).
Does the fan rotate without trouble
when handling the fan with hands?
Are resistance values between phases
at fan motor connector CN333 motor side of
indoor P.C. board (MCC-1402) correct? *1
Is resistance value of fan motor connector
CN333 at motor side of indoor P.C. board
(MCC-1402) correct? *2
Is signal output of indoor fan motor
position detection correct? *3
Check indoor P.C. board
(MCC-1402).
®
Defect
Replace
NO
YES
YES
YES
YES
YES
NO
NO
1
*
• Are not coil windings between
between
(White lead) and
3
(Black lead) and
(Red lead) opened or shorted?
5
1
®
For resistance, see the following values.
RAV-SM562, SM802, SM1102, SP562, SP802, SP1102
®
W
Approx. 70 to 100
RAV-SM1402, SP1402
• Is not earthed between cabinet and 1, 3, 5
NO
2
*
Check resistance of fan motor position detection circuit.
Is not coil winding between
®
opened or shorted?
Resistance: Approx. 5 to 20k
NO
3
*
Check fan motor position detection signal.
• Using a tester, measure the voltage between CN334
indoor P.C. board (MCC-1402) under condition that CN333 and
CN334 are mounted and the power is turned on.
®
Rotate the fan slowly with hands,
and check the pin voltage
swings between 0 to 5V voltage.
• Between
and
: 5V
4
5
– 89 –
Correct connection of connector.
Replace indoor fan motor.
Replace indoor fan motor.
1
(Red lead) and
3
(Black lead), between
5
®
W
Approx. 35 to 50
®
W
10M
Replace indoor fan motor.
(Yellow lead) and
(Pink lead)
1
4
W
Replace indoor fan motor.
CN333
(White lead),
or more
1
5
and
of
CN334