Toshiba RAV-SM562BT-E Service Manual/Integration page 37

Air conditioner split type
Hide thumbs Also See for RAV-SM562BT-E:
Table of Contents

Advertisement

RAV-SM1102UT-E, RAV-SM1102BT-E, RAV-SM1102CT-E / RAV-SP1102AT-E
Outer diameter of refrigerant pipe
Gas side ØA
Liquid side ØB
15.9mm
9.5mm
TD sensor
Accumulator
Rotary
(2500cc)
compressor
(DA420A3F – 21M)
Pressure
(MPa)
Pd
Standard
2.55
Cooling
Overload
3.28
Low load
1.76
Standard
2.58
Heating
Overload
3.43
Low load
2.10
4 poles are provided to this compressor.
*
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
* The refrigerating cycle of the indoor units differs according to
Refrigerant pipe
at gas side
Outer dia. ØA
Ball valve
Outer dia. ØA
Strainer
TS sensor
Check joint
4-way valve
(STF-0401G)
Muffler
Ø25 × L210
Ø25 × L180
Pipe surface temperature (°C)
Discharge
Suction
Ps
(TD)
(TS)
0.98
69
12
1.08
82
17
0.76
47
8
0.73
68
3
1.18
75
20
0.32
88
–14
Indoor unit
TCJ sensor
Strainer
Air heat exchanger
the models to be combined. For the refrigerating cycles of the
other indoor units, refer to the corresponding Service Manuals
described in the list on the cover.
Outdoor unit
TO sensor
TE sensor
Heat exchanger
2 row 52 stages
Outside :
Ø8 FP1.3 flat fin
Inside :
Ø9.52 FP1.5 flat fin
Indoor heat
Outdoor heat
exchanger
exchanger
(TC)
(TE)
10
40
16
48
5
27
40
3
56
16
34
–13
– 37 –
Distributor
(Strainer incorporated)
TC sensor
Refrigerant pipe
at liquid side
Outer dia. ØB
Packed valve
Outer dia. ØB
PMV
(UKV-25D22)
Distributor
R410A 2.95kg
Indoor/Outdoor temp.
Compressor
revolutions per
Indoor
second (rps)
fan
Indoor
40
HIGH
27/19
50
HIGH
32/24
24
LOW
18/15.5
44
HIGH
20/–
24
LOW
30/–
63
HIGH
15/–
Min.
Max.
5m
70m
Strainer
Cooling
Heating
conditions
(DB/WB) (°C)
Outdoor
35/–
43/–
–5/–
7/6
24/18
–15/(70%)