Check code
Wired
Outdoor 7-segment display
remote
Check code
Auxiliary code
controller
H15
H15
H16
H16
01: TK1 oil circuit system error
02: TK2 oil circuit system error
03: TK3 oil circuit system error
04: TK4 oil circuit system error
05: TK5 oil circuit system error
H25
H25
L03
L04
L04
Detected
Check code name
Status
position
I/F
Outdoor unit discharge
All stop
temp. sensor (TD2)
miswiring
I/F
Oil level detective
All stop
circuit system error
I/F
Outdoor unit discharge
All stop
temp. sensor (TD3)
miswiring
Indoor
Duplicated indoor
Corresponding
center units
unit only stops.
I/F
Duplicated outdoor
All stop
line address
Error detection condition
While compressor 2 is operating,
• Check mounting of TD2 sensor.
the discharge temp. (TD2) does
• Check connection and wiring of TD2 sensor connector.
not rise up.
• Check characteristics of TD2 sensor resistance value.
• Check outdoor unit P .C. board (I/F) error.
Temperature change of TK1 could
• Check TK1 sensor coming-off.
not be detected though
• Check characteristics of TK1 sensor resistance value.
compressor 1 started the
• Check TK1, TK2, TK3, TK4 and TK5 misconnection.
operation.
• Check operation error of SV3E, SV3F valve.
• Check capillary clogging of oil-equation circuit and operation error of stop valve.
• Check refrigerant stagnation in compressor.
Temperature change of TK2 could
• Check TK2 sensor coming-off.
not be detected though compressor
• Check characteristics of TK2 sensor resistance value.
2 started the operation.
• Check TK1, TK2, TK3, TK4 and TK5 misconnection.
• Check SV3E, SV3F valve operation.
• Check capillary clogging of oil equalization circuit and check stop valve operation.
• Check refrigerant stagnation in compressor shell.
Temperature change of TK3 could
• Check TK3 sensor coming-off.
not be detected though compressor
• Check characteristics of TK3 sensor resistance value.
started the operation.
• Check TK1, TK2, TK3, TK4 and TK5 misconnection.
• Check SV3E, SV3F valve operation.
• Check capillary clogging of oil-equalization circuit and check valve operation.
• Check refrigerant stagnation in compressor shell.
Temperature change of TK4 could
• Check TK4 sensor coming-off.
not be detected though compressor
• Check characteristics of TK4 sensor resistance value.
started the operation, or the
• Check TK1, TK2, TK3, TK4 and TK5 misconnection.
difference from other TK sensor
• Check SV3E, SV3F valve operation.
changed for a constant time only
• Check capillary clogging of oil-equalization circuit and check valve operation.
within the specified range.
• Check refrigerant stagnation in compressor shell.
Temperature change of TK5 could
• Check TK5 sensor coming-off.
not be detected though compres-
• Check characteristics of TK5 sensor resistance value.
sor started the operation, or the
• Check TK1, TK2, TK3, TK4 and TK5 misconnection.
difference from other TK sensor
• Check SV3E valve operation error.
changed for a constant time only
• Check capillary clogging of oil-equalization circuit and check valve operation error.
within the specified range.
• Check refrigerant stagnation in compressor.
While compressor 2 is operating,
• Check mounting of TD3 sensor.
the discharge temp. (TD3) does
• Check connection and wiring of TD3 sensor connector.
not rise up.
• Check characteristics of TD3 sensor resistance value.
• Check outdoor unit P .C. board (I/F) error.
There are multiple center units in a
• Check indoor address.
group.
• Check the change of remote controller connection
(Group/individual) after indoor address setup.
Line address setup is duplicated
• Check line address.
against the outdoor unit in different
refrigerant pipe system.