8-4. Check Code and Check Position Displayed on the Remote Controller and Outdoor Unit
(7-Segment Display of Interface)
<In case of SUPER MODULAR MULTI SYSTEM>
Check code
Wired
Outdoor 7-segment display
remote
controller
Check code
Auxiliary code
E01
E02
E03
E04
E06
E06
No. of indoor units
which received
signal normally
E07
E08
E08
Duplicated indoor
addresses
E09
E10
E12
E12
01: Indoor/outdoor
communication
02: Between outdoors
communication
Detected
Check code name
Status
position
Remote
Communication error between
Corresponding
controller
indoor and remote controller
unit only stops.
(Detected at remote controller
side)
Remote
Remote controller sending
Corresponding
controller
error
unit only stops.
Indoor
Communication error between
Corresponding
unit
indoor and remote controller
unit only stops.
(Detected at indoor side)
Indoor
Indoor/outdoor communication
Corresponding
unit
circuit error
unit only stops.
(Detected at indoor side)
I/F
Decreased number of indoor
All stop
units
Indoor/outdoor communication
I/F
All stop
circuit error
(Detected at outdoor side)
Indoor
Duplicated indoor addresses
All stop
I/F
Remote
Duplicated master remote
Corresponding
controller
controllers
unit only stops.
Indoor
Communication error between
Corresponding
unit
indoor P .C. board assembly
unit only stops.
I/F
Automatic address start error
All stop
Error detection condition
Communication interrupted between indoor
• Check remote controller inter-unit cable (A/B).
P .C. board and remote controller.
• Check disconnection, connector contact error.
• Check indoor power supply.
• Check indoor P .C. board error.
• Check remote controller address setup.
(When two remote controllers operate)
• Check remote controller P .C. board.
Signal could not be sent from remote
• Check the communication wire of remote controller:
controller to indoor unit.
Exchange remote controller.
No communication from remote controller
• Check remote controller and communication adapter wiring.
(including wireless) and communication
adapter.
Indoor unit does not receive communication
• Check power-ON order of indoor/outdoor.
from outdoor unit.
• Check indoor address setup.
• Check inter-unit cabling between indoor and outdoor.
• Check outdoor end terminal resistance setup (SW30-2).
When signal is not sent for a certain period
• Check the power supply of indoor unit. (Power-ON)
from the indoor unit which has been used to
• Check connection of communication line between indoor and outdoor.
send signals.
• Check connector connection for communication in indoor P .C. board.
• Check connector connection for communication in outdoor P .C. board.
• Check indoor P .C. board failure.
• Check outdoor P .C. board (I/F) failure.
Transmission from outdoor to indoor cannot
• Check outdoor terminator resistor setup (SW30-2).
continue for 30 seconds.
• Check the communication connection between indoor and outdoor.
Multiple indoor unit address setup are
• Check indoor address.
duplicated.
• Check the change of remote controller connection (Group / individual)
after setup of indoor address.
In 2-remote controller control (including
• Check remote controller setup.
wireless), both are setup as master
• Check remote controller P .C. board.
(Header indoor unit stops and other indoor
unit is operating.)
Communication was not succeeded after
• Indoor P .C. board failure
power was supplied or during
communication.
• When indoor automatic address started,
• Setup the address again after disconnecting communication
other refrigerant circuit system was setting
connection with other refrigerant circuit system.
automatic address.
• When outdoor automatic address started,
indoor automatic address was executed.
Check item (position)