Toshiba MMK-AP0074MH-E Service Manual page 46

Hide thumbs Also See for MMK-AP0074MH-E:
Table of Contents

Advertisement

[Remote controller detects error.]
Check code display
Outdoor 7-segment
Remote controller
Auxiliary code
E01
E02
E09
[Central controller detects error.]
Check code display
Outdoor 7-segment
TCC-LINK central
Auxiliary code
C05
C06
C12
P30
Note) The check code display may be different according to the detected device even same error contents such as communication error.
Sensor lamp display
Block display (∗)
Operation Timer Ready
Flash
No remote controller header unit, remote controller
l
l
¥
communication (receive) error
l
l
¥
Remote controller communication (send) error
l
l
¥
Duplicated remote controller header
Sensor lamp display
Block display (∗)
Operation Timer Ready
Flash
Central control system communication (send) error
Is not displayed
(In shared use
Central control system communication (receive) error
of remote controller)
There are multiple network adapters.
Batched alarm of interface for general-purpose equipment control
According to unit with alarm
Group follower unit error
(Abovementioned)
(∗) ¡: Goes on, ¥: Flashes, l: Goes off
A (Alternate)
S (Simultaneously) : Two LED flash simultaneously when there are two flashing LED.
Main defective position
When signal cannot be received from indoor unit, when header of remote
controller was not set (including 2 remote controllers)
When signal cannot be sent to indoor unit
In 2-remote controller control, both remote controllers were set to header.
(Indoor header stops with alarm and follower unit continues operation.)
Main defective position
When signal of central control system cannot be sent, there are same multiple
central devices (AI-NET)
When signal of central control system cannot be received
There were multiple network adapters (AI-NET) on remote controller
communication line.
Error of equipment connected to control interface of the general-purpose unit
exclusive to TCC-LINK/AI-NET
Group follower unit error
(For remote controller, [
: Flashing condition is alternate when there are two flashing LED.
Description
Description
∗∗∗
] details is displayed together with unit No.)