Communication Examples - ABB COMMANDER 300 Operating Instructions Manual

Universal process controller serial data communication supplement
Hide thumbs Also See for COMMANDER 300:
Table of Contents

Advertisement

8.4

Communication Examples

The following examples show typical master-to-slave transmissions and the subsequent slave-
to-master replies. For
a)
Command –
STX
STX
R
06
PB ETX
Proportional band
Controller number six
'Read' command
Start of text
Reply – 06PB100.0
06
PB 100.0
ACK
Proportional band is 100%
Controller number 06
b)
Command –
STX
STX
R
07
IX ETX
Parameter 'IX'
Controller number seven
'Read' command
Start of text
Reply – 0702
NAK
07
02 NAK
Command not understood
Error code 2
Controller number seven
i.e. 'IX' in the original command is not a
recognised 'Read' parameter – see
Section 8.6.
and
Error Code
Parameter
R06PB
E E TX
End of text
ACK
Command understood
R07IX
E E TX
End of text
8 COMMUNICATION...
interpretations refer to Sections 8.5 and 8.6.
c) Command –
STX
STX
M
05
MG ETX
Multiple read mnemonic
Controller number five
'Multiple Read' command
Start of text
Reply:
Controller number 5
Command understood
05 MV 60.0
ACK
ETB
05 IS 0
ETB
05 SP 65.0
ACK
ETB
05 OP 72.5
ACK
ETB ACK
ACK
End of transmission block
* '0' is the normal status – see Fig. 8.7
overleaf.
d) Command –
STX
STX
M
05
MV ETX
Measured (process) Variable
Controller number five
'Multiple Read' command
Start of text
Reply – 0519
N N AK
05 19
NAK
Command not understood
Error code 19
Controller number five
i.e. the 'Multiple Read' command cannot
be used for a single parameter – see
Section 8.6.
M05 MG
E E TX
End of text
Measured value 60.0
Instrument status 0 *
Control setpoint 65.0
Control output 72.5%
M05MV
ETX
End of text
9