ABB COMMANDER 300 Operating Instructions Manual page 15

Universal process controller serial data communication supplement
Hide thumbs Also See for COMMANDER 300:
Table of Contents

Advertisement

8.6.1 General Parameters...
Parameter
Time Units
Cycle Time
Hysteresis Value
Proportional Band
Integral Action Time
Derivative Action Time
Approach Band
P.I.D. Offset
Local Set Point Adjust
Enable
Local Set Point High
Limit
Local Set Point Low
Limit
Local Set Point
Set Point Tracking
Enable
Set Point Type Select
State
Second Set Point State
Dual Set Point High
Limit
Dual Set Point Low
Limit
Remote Set Point High
Limit
Remote Set Point Low
Limit
Ratio Adjust Enable
(Remote Set Point)
Ratio Adjust Value
(Remote Set Point)
Bias Adjust Enable
(Remote Set Point)
Bias Adjust Value
(Remote Set point)
Select Set Point Type
Command
Mnemonic
Read
(R)
Control Page Parameters
TU
Yes
CT
Yes
HY
Yes
PB
Yes
IT
Yes
DT
Yes
AB
Yes
OF
Yes
Set Point Parameters
SE
Yes
SH
Yes
SL
Yes
LP
Yes
TE
Yes
TS
Yes
UE
Yes
UH
Yes
UL
Yes
MH
Yes
ML
Yes
RE
Yes
RO
Yes
BE
Yes
BO
Yes
TY
Yes
8 COMMUNICATION...
Reply Interpretation
Write
(W)
Yes
0 = Seconds
1 = Minutes
Yes
1.0 to 300.0 seconds (0.9 = ON/OFF)
Yes
0.0 to 5.0(%)
Yes
0.1 to 999.9
Yes
1 to 7200 seconds, 7201 = OFF
Yes
1 to 999.9 seconds, 0 = OFF
Yes
0.1 to 3.0
Yes
0 = 0.0
1 = 50.0
Yes
0 = No
1 = Yes
Yes
Any value within the programmed display range
Yes
Any value within the programmed display range
Yes
Any value within the programmed display range
Yes
0 = No
1 = Yes
Yes
0 = No
1 = Yes
Yes
0 = None
1 = Dual
2 = Remote
Yes
Any value within the programmed display range
Yes
Any value within the programmed display range
Yes
Any value within the programmed display range
Yes
Any value within the programmed display range
Yes
0 = No
1 = Yes
Yes
0.010 to 9.999
Yes
0 = No
1 = Yes
Yes
–100 to +100
Yes
0 = Local
1 = Balance
2 = Second
13