Profile Parameters - ABB COMMANDER 300 Operating Instructions Manual

Universal process controller serial data communication supplement
Hide thumbs Also See for COMMANDER 300:
Table of Contents

Advertisement

8.6.2 Profile Parameters

Parameter
Profile Status
Countdown Time
Current Programme
Current Segment
Segment Time
Prog. Repeat Count
First Prog. Select
Second Prog. Select
Third Prog. Select
Fourth Prog. Select
Time Delay
Profile Start
Hold State
Profile Reset
Skip
Operator Hold
Command
Mnemonic
Read
(R)
Profile Parameters
PS
Yes
CD
Yes
PP
Yes
PG
Yes
PT
Yes
PR
Yes
1P
Yes
2P
Yes
3P
Yes
4P
Yes
TD
Yes
GP
Yes
PH
Yes
RT
Yes
PK
Yes
PO
Yes
8 COMMUNICATION...
Reply Interpretation
Write
(W)
No
0 = Stop
1 = Ramp
2 = Soak
3 = Not Used
4 = Countdown
5 = Operator Hold
6 = Not Used
7 = Manual Hold
8 = Holdback Hold
9 = End
No
Time (in Minutes)
No
1 to 9
No
0 to 30
No
Time (in Minutes)
No
0 to 99 (100 = Always)
Yes
1 to 9 (10 = None)
Yes
1 to 9 (10 = None)
Yes
1 to 9 (10 = None)
Yes
1 to 9 (10 = None)
Yes
0.0 to 999.9 minutes
Yes
1 = Start
No
Bit 0 = Operator Hold
Bit 2 = Manual Mode Hold
Bit 3 = Holdback Hold
Yes
1 = Reset Profile
Yes
1 = Skip
Yes
1 = Operator Hold
19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents