Baxi Solo 12 HE Installation And Servicing Instructions page 53

Wall mounted powered flue condensing boilers gas fired central heating units
Table of Contents

Advertisement

OVERHEAT LOCKOUT
Disconnect
black stat on flow pipe.
When flow < 60° C is there
continuity across stat ?
YES
Reconnect stat.
Disconnect fan stat.
When fan temp < 60° C
is there continuity
across stat ?
YES
Reconnect stat.
Disconnect the larger of
the 6-way PCB connectors.
Is there continuity
across M ?
YES
Disconnect
thermistor
(red sensor on flow pipe).
Is resistance between
0.5kΩ & 20kΩ ?
YES
Is
combustion chamber
door seal damaged or not in
place ?
NO
Replace PCB.
© Baxi Heating UK Ltd 2006
Lights
Flash Off On
ON
NO
Replace Stat.
NO
Replace Stat.
NO
Wiring from PCB to
thermostats faulty.
NO
Replace thermistor.
YES
Replace combustion
chamber door seal & trim
seal.
17.0
Fault Finding
M
6-way Connector
53

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Solo 18 heSolo 15 heSolo 24 heSolo 30 he

Table of Contents