8.0
Installation - Page 19
8.4 Fitting The Boiler (Fig. 24)
1. Remove the tape from the tap rail on the support bracket
and fit the central heating return filter (Fig. 25).
2. Lift the boiler using the lower edges of the combustion
box.
3. Lift the boiler over the support bracket and engage onto
the top hooks.
4. To gain access to the connections between boiler and
valves, release the facia securing screws (¼ turn) and hinge
down the facia box.
5. Make the gas connection first. This will centralise the
boiler. The gas sealing washer is an integral part of the gas
tap.
6. Insert the fibre sealing washers between the valve outlet
face and the flange on the copper bends of the water circuit
connections.
7. Tighten the connections.
8.5 Making the Condensate Drain Connection
1. Connect the condensate drain using the 1" BSP nut and
seal supplied. (see section 7.8.)
2. For better access, loosen the left hand electrical
box/transformer mounting plate securing screws and remove
the right hand securing screw. Slide the electrical box to the
right (Fig. 25b).
NOTE: To ensure the correct operation and integrity of
the condensate drainage system
- Carefully pour approximately 1 litre of water into the
flue products exhaust, at the top of the heat exchanger
(Fig. 25a).
Check the condensate drain for leaks, blockage and fall.