[ II Restrictions ]
II Restrictions

[1] System configuration

1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
Outdoor
Composing units
units
72
-
96
-
120
-
144
72
168
96
192
96
216
120
240
120
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
HWE0803A
Maximum total capacity
of connectable indoor
units
-
36 - 108
-
48 - 144
-
60 - 180
72
72 - 216
72
84 - 252
96
96 - 288
96
108 - 324
120
120 - 360
- 17 -
Maximum number
Types of connectable in-
of connectable in-
door units
door units
18
P06 - P96 models
R410A series indoor units
24
30
36
42
48
50
50
GB