[ IX Troubleshooting ]
2. Phenomena
Although heating operation starts with the normal remote controller display, the capacity is not enough.
(1) Cause, check method and remedy
1.
Compressor frequency does not rise sufficiently.
Faulty detection of pressure sensor.
Protection works and compressor frequency does
not rise due to high discharge temperature
Protection works and compressor frequency does
not rise due to high pressure.
HWE0803A
Cause
- 267 -
Check method and remedy
(1)
Check pressure difference between the detected
pressure by the pressure sensor and the actual
pressure with self-diagnosis LED.
-> If the accurate pressure is not detected, check
the pressure sensor.(Refer to the page on Trouble-
shooting of Pressure Sensor)
Note:
Higher inlet pressure by the high pressure sensor
than the actual pressure causes insufficient capac-
ity.
SW1 setting
High pressure sensor
SW1
ON
Low pressure sensor
SW1
ON
(2)
Check the difference between the condensing tem-
perature (Tc) and the target condensing tempera-
ture (Tcm) with self-diagnosis LED.
Note:
Higher Tc than Tcm causes insufficient capacity.
SW1 setting
Condensing temperature Tc
ON
Target condensing temperature Tcm
ON
Note:
Protection works and compressor frequency does
not rise even at lower Tc than Tcm due to high dis-
charge temperature and high pressure.
At high discharge temperature:
Refer to 1102.(page 184)At high pressure:
Refer to 1302.(page 186)
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
SW1
1 2 3 4 5 6 7 8 9 10
SW1
1 2 3 4 5 6 7 8 9 10
GB