[ VIII Test Run Mode ]
Model name of BC controller
Ambient
tempera-
ture
Indoor unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
ing
BC controller (1/2/3)
High pressure(63HS1)/
Low pressure(63LS)
Pressure
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
Outdoor
unit
Temp. of
each sec-
tion
Indoor unit
HWE0803A
Operation
Indoor
DB/WB
Outdoor
No. of connected units
No. of units in operation
Model
Main pipe
Branch pipe
Total pipe length
[lbs-oz]
Pulse
Discharge (TH4)
Heat exchanger outlet
(TH6)
Accumulator inlet
Accumulator outlet
Compressor inlet
Compressor shell bottom
LEV inlet
Heat exchanger inlet
- 175 -
Outdoor unit model
PURY-P216TSHMU-A
PURY-P120THMU-A
CMB-P1013NU-GA
21.1°C/- [70°F/-]
8.3°C/6.1°C [47°F/43°F]
Unit
-
36/36/36/36/36/36
m
[ft]
-
kg
A
V
Hz
81
350/350/350/350/350/350
110/110/1120
2.62/0.64
[380/92]
MPa
[psi]
73 [163]
2 [36]
-1 [30]
°C
-1 [30]
[°F]
-1 [30]
40 [104]
PURY-P96THMU-A
6
6
5 [16-3/18"]
10 [32-3/4"]
65 [213-1/4"]
Hi
43.0 [95]
54.0
230
71
2.62/0.68
[380/98]
2.60/2.27
[377/329]
80 [176]
0 [32]
-2 [28]
-3 [27]
-3 [27]
40 [104]
33 [91]
68 [154]
GB