Mitsubishi Electric PURY-P72 Service Handbook page 174

Hide thumbs Also See for PURY-P72:
Table of Contents

Advertisement

[ VIII Test Run Mode ]
(2) Heating only operation
Model name of BC controller
Ambient
tempera-
ture
Indoor unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
ing
BC controller (1/2/3)
High pressure(63HS1)/
Low pressure(63LS)
Pressure
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
Outdoor
unit
Temp. of
each sec-
tion
Indoor unit
HWE0803A
Operation
Indoor
DB/WB
Outdoor
No. of connected units
No. of units in operation
Model
Main pipe
Branch pipe
Total pipe length
[lbs-oz]
Pulse
Discharge (TH4)
Heat exchanger outlet
(TH6)
Accumulator inlet
Accumulator outlet
Compressor inlet
Compressor shell bottom
LEV inlet
Heat exchanger inlet
- 165 -
Outdoor unit model
PURY-P72THMU-A
CMB-P104NU-G
21.1°C/-
[70°F/-]
8.3°C/6.1°C
[47°F/43°F]
3
Unit
3
-
24/24/24
5 [16-3/8"]
m
10 [32-3/4"]
[ft]
35 [114-13/16"]
-
Hi
kg
19.1 [42]
A
16.8
V
230
Hz
48
205/203/200
110/-/520
2.61/0.69
[378/100]
MPa
[psi]
2.54/2.22
[368/321]
69 [156]
0 [32]
1 [34]
°C
1 [34]
[°F]
1 [34]
40 [104]
30 [86]
63 [145]
PURY-P96THMU-A
CMB-P104NU-G
21.1°C/-
[70°F/-]
8.3°C/6.1°C
[47°F/43°F]
2
2
48/48
5 [16-3/8"]
10 [32-3/4"]
25 [82]
Hi
21.3 [47]
24.1
230
71
406/406
110/-/590
2.67/0.68
[387/98]
2.63/2.31
[381/335]
80 [176]
0 [32]
-2 [28]
-3 [27]
-3 [27]
40 [104]
38 [100]
70 [158]
GB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents