[ IV Remote Controller ]

[2] Group Settings and Interlock Settings via the ME Remote Controller

1. Group settings/interlock settings
Make the following settings to perform a group operation of units that are connected to different outdoor units or to manually set up the
indoor/outdoor unit address.
(A) Group settings...........Registration of the indoor units to be controlled with the remote controller,
and search and deletion of registered information.
(B) Interlock settings........Registration of LOSSNAY units to be interlocked with the indoor units,
and search and deletion of registered information
[Operation Procedures]
(1) Address settings
Register the indoor unit to be controlled with the remote controller.
1
Bring up either the blinking display of HO by turning on the unit or the
normal display by pressing the ON/OFF button.
The display window must look like one of the two figures below to proceed to the
next step.
[Blinking display of HO ]
(A) Group Settings
Bring up the Group Setting window.
2
-Press and hold buttons
[FILTER] and
A
simultaneously for 2 seconds to bring up the display as
shown below.
3
Select the unit address.
-
Select the address of the indoor unit to be registered by pressing
button
C
[TEMP. (
) or (
through the addresses.
4
Register the indoor unit whose address appears on the
display.
- Press button
[TEST] to register the indoor unit address
D
whose address appears on the display.
- If registration is successfully completed, unit type will appear
on the display as shown in the figure below.
- If the selected address does not have a corresponding indoor
unit, an error message will appear on the display. Check the
address, and try again.
<Successful completion of registration>
<Deletion error>
blinks to indicate a registration error.
(Indicates that selected address does not have a
corresponding unit.)
5
To register the addresses for multiple indoor units, repeat
steps
and
above.
3
4
To search for an address,
go to section (2) Address Search.
To next page.
HWE0803A
[Normal display]
[
]
B
Indoor unit address display window
)] to advance or go back
Unit type (Indoor unit in this case)
C
G
E
(B) Interlock Settings
6
Bring up the Interlock Setting window.
-Press button
[
G
Press again to go back to the Group Setting window as shown
under step
.
2
Indoor unit
Interlocked unit
address
address
display window
display window
7
Bring up the address of the indoor unit and the address of the
LOSSNAY to be interlocked on the display.
- Select the address of the indoor unit to be registered by pressing
button
[TEMP. ( ) or ( )] to advance or go back through
C
the addresses.
- Select the address of the LOSSNAY unit to be interlocked by
pressing button
[TIMER SET ( ) or ( )] to advance or go back
H
through the interlocked unit addresses.
8
Make the settings to interlock LOSSNAY units with indoor
units.
- Press button
[TEST] while both the indoor unit address and
D
the address of the LOSSNAY units to be interlocked
are displayed to enter the interlock setting.
- Interlock setting can also be made by bringing up the
LOSSNAY address in the indoor unit address display
window and the indoor unit address in the interlocked unit
address display window.
(Displayed alternately)
NOTE : Interlock all the indoor units in the group with the
LOSSNAY units; otherwise, the LOSSNAY units will
not operate.
- 84 -
CENTRALLY CONTROLLED
1Hr.
ON OFF
DAILY
˚C
AUTO OFF
CLOCK
REMAINDER
FILTER
CHECK MODE
TEST RUN
STAND BY
˚C
NOT AVAILABLE
LIMIT TEMP.
DEFROST
TEMP.
ON/OFF
?
CLOCK→ON→OFF
FILTER
CHECK TEST
TIMER SET
PAR-F27MEA
D
H
B
] to bring up the following display.
Both the indoor unit address and
interlocked unit address will be
displayed together.
To search for an address,
go to section (2) Address Search.
If registration is successfully
completed, the two displays as
shown on the left will appear
alternately.
If the registration fails,
will blink on the display.
(Indicates that the selected
address does not have a
corresponding unit.)
F
A
GB