Table 12
Group settings and values (continued)
Group
Item:
1
Group 3:
User
2
Settings
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
1 to
Group 4:
63
Event Mask
64 to
Settings
143
Description
SRC1 Fast Undervoltage
Setpoint
SRC1 Slow Undervoltage
Setpoint
SRC1 Slow Undervoltage
Detect Delay
SRC1 Overvoltage
Setpoint
SRC1 Overvoltage Detect
Delay
SRC1 I peak Transfer
Setpoint
SRC2 Fast Undervoltage
Setpoint
SRC2 Slow Undervoltage
Setpoint
SRC2 Slow Undervoltage
Detect Delay
SRC2 Overvoltage
Setpoint
SRC2 Overvoltage Detect
Delay
SRC2 I peak Transfer
Setpoint
Max. Transfer Phase
Angle
Output Frequency
Deviation
ReTransfer Delay Time
Horn Volume
Critical Option Enabling
Non-Critical Option
Enabling
Event Mask settings for
faults
Event Mask settings for
alarms
80
Value Type
Integer
In % of nominal below nominal
Integer
In % of nominal below nominal
Integer
In number of lines cycles
Integer
In % of nominal above nominal
Integer
In 1/4 lines cycles
Integer
x 10
Integer
In % of nominal below nominal
Integer
In % of nominal below nominal
Integer
In number of lines cycles
Integer
In % of nominal above nominal
Integer
In 1/4 lines cycles
Integer
x 10
Integer
In degrees
Integer
Freq. in Hz x 10
Integer
In seconds
Integer
Range: 1-10
Bitpacked
See section 12.1.3.
Bitpacked
See section 12.1.3.
Event Mask
See section 12.1.4.
Event Mask
See section 12.1.4.
Communication Interfaces
Value Notes