5. Once the UPS is in the desired location, adjust the leveling feet to secure its position.
2.2.2

Stationary Mounting

Additional stability can be added by bolting the mounting brackets (used in shipping) to the floor, as
shown below left.
Shipping Brackets Used
for Stationary Mounting
For greater stability, use a higher-grade bolt. Refer to the dimensions above right when drilling holes
for stationary mounting.
1/2" (13mm)
28"
(711mm)
10
Optional Stationary
Mounting Dimensions
4.75"
4.75"
(120mm)
(120mm)
5/16" (7.94mm)
diameter - in six
places