Major Components; Unit Frame; User Interface Module; System Control Module - Liebert NfinityTM User Manual

105/210v 50/60hz 4 to 16 kva power system
Table of Contents

Advertisement

1.3

Major Components

The following is a general description of each compo-
nent and its functions. Please review this section
carefully, as it will give you a better understanding as
to how the Nfinity operates.
1.3.1

Unit Frame

The front of the Nfinity consists of a series of plastic
bezels. By grasping these bezels from the left and
right sides and pulling straight out, you can remove
the bezel to reveal the Battery / Power Module bays.
The bottom bezel covers the internal cooling fans and
the manual bypass switch.
The User Interface Module is located above the
Power / Battery Module bays for easy access. By mov-
ing the User Interface and setting it on top of the
frame, you will see the system control module bays.
NOTE
In the figure at right, the Power Module and
Battery Module are extended for illustration
purposes only. Extending more than one
module at a time could cause the unit to be
top-heavy and/or tip.
1.3.2

User Interface Module

The User Interface Module is the primary source of
communication between the UPS and the user. From
the interface, the user can:
• View the status of the UPS
• Custom configure the system
• Review the event log to assist with
troubleshooting
• Enable/disable the output power
• Silence the audible alarm
• Manually transfer the unit to bypass
For a more detailed explanation on how to operate the
User Interface Module, see 3.1 - Controls and Indi-
cators.
1.3.3

System Control Module

The System Control Module is the communications
backbone of the UPS. It gathers input from all mod-
ules and processes the data to control the operation of
the system — including monitoring the condition of
each module. An optional redundant System Control
Module can be installed to provide full system func-
tionality (operation and communication).
Under normal operation, the Status LED (green) will
blink and the Fault LED (yellow) will be off. For any
condition other than this, check 4.0 - Troubleshoot-
ing.
Fault LED
Status LED
6
Introduction
Nfinity's frame
with bezels removed
User Interface Module
System Control Module
Fasteners
Lever

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nfinity

Table of Contents