Ups Configuration Screen - Liebert Nfinity User Manual

208/240v 60hz 4 to 16 kva
Hide thumbs Also See for Nfinity:
Table of Contents

Advertisement

3.5.2

UPS Configuration Screen

Review Settings
Follow this procedure to review your UPS configuration settings. Follow the menus below by pressing
and
to review the settings.
Voltage
Voltage Settings
Input 208/120
Output 208
Frequency
Frequency Settings
Frequency Hz: 60
Sync Range Hz: +/- 5.0
Slew Range Hz/S: 3.0
Battery
Battery Settings
Test intrvl weeks: 2
on Wed 06:00
Low Batt Warn:2 min
Alarm
Alarm Settings
Redundant Alarm:
Enabled/Disabled
Max Load: Enabled/Disabled
Main Menu
UPS Status
> UPS Configuration
Display Date/Time
Event Log
Active Alarms
Transfer to Bypass
Module Replacement
Service Tools
UPS Configuration
UPS Configuration
> Review Settings
Change Settings
Service Mode
Review Settings
Voltage
Frequency
Battery
Alarm
Service Contact
Auto Restart
UPS Shutdown Delay
Remote Shutdown
External Battery
Bypass Alarm Mode
Intelli-Battery Ca.
Air Filter Reminder
Guarantee Shutdown
Review Settings menu options
Service Contact
Service Contact
Liebert Corp.
www.liebert.com
Auto Restart
Auto Restart
Mode:
Disable
Batt %
0%
Delay
10
UPS Shutdown Delay
UPS Shutdown Delay
120 seconds
Remote Shutdown
Remote comm shutdown
Mode: Enable
22
Operating Instructions
External Battery
External batt config
Amp.Hr
0000
Charge (A) 00.0
Bypass Alarm Mode
Bypass Alarm Mode
Mode:
Enable
Intelli-Battery Ca.
Intelli-Batteries
0
Air Filter Reminder
Air Filter Reminder
Mode:
26 weeks
Guarantee Shutdown
Guarantee Shutdown
Mode: Enable/Disable