3.5.2
UPS Configuration Screen
Review Settings
Follow this procedure to review your UPS configuration settings. Follow the menus below by pressing
and
to review the settings.
Voltage
Voltage Settings
Input 208/120
Output 208
Frequency
Frequency Settings
Frequency Hz: 60
Sync Range Hz: +/- 5.0
Slew Range Hz/S: 3.0
Battery
Battery Settings
Test intrvl weeks: 2
on Wed 06:00
Low Batt Warn:2 min
Alarm
Alarm Settings
Redundant Alarm:
Enabled/Disabled
Max Load: Enabled/Disabled
Main Menu
UPS Status
> UPS Configuration
Display Date/Time
Event Log
Active Alarms
Transfer to Bypass
Module Replacement
Service Tools
UPS Configuration
UPS Configuration
> Review Settings
Change Settings
Service Mode
Review Settings
Voltage
Frequency
Battery
Alarm
Service Contact
Auto Restart
UPS Shutdown Delay
Remote Shutdown
External Battery
Bypass Alarm Mode
Intelli-Battery Ca.
Air Filter Reminder
Guarantee Shutdown
Review Settings menu options
Service Contact
Service Contact
Liebert Corp.
www.liebert.com
Auto Restart
Auto Restart
Mode:
Disable
Batt %
0%
Delay
10
UPS Shutdown Delay
UPS Shutdown Delay
120 seconds
Remote Shutdown
Remote comm shutdown
Mode: Enable
22
Operating Instructions
External Battery
External batt config
Amp.Hr
0000
Charge (A) 00.0
Bypass Alarm Mode
Bypass Alarm Mode
Mode:
Enable
Intelli-Battery Ca.
Intelli-Batteries
0
Air Filter Reminder
Air Filter Reminder
Mode:
26 weeks
Guarantee Shutdown
Guarantee Shutdown
Mode: Enable/Disable