Turbo Air TAS-09EH/O Service Manual

Turbo Air TAS-09EH/O Service Manual

Dc inverter multi-split air-condition unit
Hide thumbs Also See for TAS-09EH/O:

Advertisement

SERVICE
TAS-09EH/O
TAS-12EH/O
DC Inverter Multi-Split Air-Condition Unit
TAS-18EH/O
TAS-18MVH/O
Indoor Unit
TAS-09MVH
TAS-12MVH
TAS-09EH
TAS-12EH
TAS-18EH
TAS-24EH
REFRIGERENT
R410A
MANUAL
TAS-24EH/O
Outdoor Unit
TAS-18MVH/O
TAS-24MVH/O
TAS-09EH/O
TAS-12EH/O
TAS-18EH/O
TAS-24EH/O
1
TAS-24MVH/O
HEAT PUMP
SERVICE MANUAL FOR AMERICA

Advertisement

Table of Contents
loading

Summary of Contents for Turbo Air TAS-09EH/O

  • Page 1 SERVICE MANUAL DC Inverter Multi-Split Air-Condition Unit TAS-09EH/O TAS-12EH/O TAS-18EH/O TAS-24EH/O TAS-24MVH/O TAS-18MVH/O Indoor Unit Outdoor Unit TAS-09MVH TAS-12MVH TAS-18MVH/O TAS-24MVH/O TAS-09EH TAS-09EH/O TAS-12EH TAS-12EH/O TAS-18EH TAS-18EH/O TAS-24EH TAS-24EH/O REFRIGERENT HEAT PUMP R410A SERVICE MANUAL FOR AMERICA...
  • Page 2: Table Of Contents

    Table of Contents INTRODUCTION ....................1-1 PRODUCT DATA SHEET ..................2-1 RATING CONDITIONS ..................3-1 OUTLINE DIMENSIONS ..................4-1 PERFORMANCE DATA ..................5-1 PRESSURE CURVES ..................6-1 ELECTRICAL DATA ....................7-1 WIRING DIAGRAMS .................... 8-1 REFRIGERATION DIAGRAMS ................9-1 10. TUBING CONNECTIONS ..................10-1 11.
  • Page 3: Introduction

    INTRODUCTION General The new CMV and CS is a high efficiency DC inverter technology outdoor unit, since it’s a lego concept unit, it can be matched to several inverter indoor units such as wall mounted type with a capacity range of 9000 – 12000 BTU for each single indoor unit. Main Features DC Inverter R410a...
  • Page 4: Product Data Sheet

    P R O D U C T D A T A S H E E T 2 . 1 O u t d o o r u n i t d a t a 2 . 1 .1 D C I n v e r t o r 1 : 1 . Item DC INVERTER 1:1 Capacity (BTU)
  • Page 5 2 . 1 .2 D C I n v e r t e r 1 : 2 TAS-18MVH/O TAS-24MVH/O Heat Pump Heat Pump Function 208-230 VAC 208-230 VAC Rated Voltage 60 Hz 60 Hz Rated Frequency Circuit Breaker Size Op Range Cool °F 5~131 5~131 minus 4 ~ 109...
  • Page 6 2 . 2 I n d o o r U n i t s D a t a TAS-09MVH 2 . 2 . 1 S p e c i f i c a t i o n s TAS-09MVH YDK-16-4C Model Input (W) 1.2/450VAC...
  • Page 7: Rating Conditions

    Cooling Upper limit (DB) Lower limit (DB) Heating Upper limit (DB) Lower limit (DB) 198–264V/115V Voltage O U T L I N E D I M E N S I O N S outdoor Unit: TAS-09EH/O SERVICE MANUAL FOR AMERICA...
  • Page 8 outdoor Unit: TAS-12EH/O 4.3 outdoor Unit: TAS-18EH/O 4.4 outdoor Unit: TAS-24EH/O SERVICE MANUAL FOR AMERICA...
  • Page 9 4.5 outdoor Unit: TAS-18MVH/O SERVICE MANUAL FOR AMERICA...
  • Page 10: Performance Data

    4.7 outdoor Unit: TAS-24MVH/O P E R F O R M A N C E D A T A Indoor Units Data 5.1.1 Indoor Units Capacity For 9000BTU Capacity Model TAS-09MVH 9000BTU TAS-09EH 5.1.1.1 Cooling Capacity (BTU)---Run Model (Unit A,B,C or D),230/115V,Indoor fan at high speed INDOOR ENTERING AIR DB/WB TEMPERATURE [ OUTDOOR...
  • Page 11 (protection range) 80 - 105 % of nominal 25 - 50 % of nominal 8712 9252 9828 10404 10980 6273 6382 6528 6638 6784 0.58 0.59 0.61 0.62 8280 8856 9432 9972 10548 6091 6236 6346 6492 6601 0.65 0.66 0.67 0.68 0.69...
  • Page 12 85 - 105 % of nominal 59~75 (Protection Range) 80 - 120 % of nominal 5.1.1.3 Capacity Correction Factors Cooling Capacity Ratio Vs. Outdoor Temperature Cooling Capacity Correction Factor 90/73 84/70 81/66 75/63 72/59 Outdoor Temp.(deg F) Heating Capacity Ratio Vs. Outdoor Temperature Heating Capacity Correction Factor Outdoor Temp.(deg F) SERVICE MANUAL FOR AMERICA...
  • Page 13 5.2.1 Indoor Units Capacity For 12000BTU Capacity Model 12000BTU TAS-12MVH TAS-12EH 5.2.1.1 Cooling Capacity (BTU)---Run Model (Unit A,B,C or D),230/115V,Indoor fan at high speed INDOOR ENTERING AIR DB/WB TEMPERATURE [ OUTDOOR ENTERING AIR DB TEMPERATURE[ DATA 72/59 75/63 81/66 84/70 90/73 80 - 110 % of nominal 14~68...
  • Page 14 5.2.1.2 Heating Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at high speed ID COIL ENTERING AIR DB TEMPERATURE [ OD COILENTERING AIR DB/WB TEM DATA PERATU RE[ 8960 8260 7700 0.66 0.73 0.80 9940 9240 8680 14/10 0.80 0.87 0.95 10640 10080...
  • Page 15 Heating Capacity Ratio Vs. Outdoor Temperature Heating Capacity Correction Factor Outdoor Temp.(deg F) 5.2.3 Indoor Units Capacity For 18000BTU Capacity Model 18000BTU TAS-18EH 5.2.3.1 Cooling Capacity (BTU)---Run Model ,230V,Indoor fan at high speed INDOOR ENTERING AIR DB/WB TEMPERATURE [ OUTDOOR ENTERING AIR DB TEMPERATURE[0F] DATA...
  • Page 16 5.2.3.2 Heating Capacity (BTU)---Run Model,230V,Indoor fan at high speed ID COIL ENTERING AIR DB TEMPERATURE [ OD COILENTERING AIR DB/WB TEM DATA PERATU RE[ 12160 11210 10450 0.96 1.05 1.15 13490 12540 11780 14/10 1.15 1.25 1.37 14440 13680 12730 20/18 1.31 1.40...
  • Page 17 Heating Capacity Ratio Vs. Outdoor Temperature Heating Capacity Correction Factor Outdoor Temp.(deg F) 5.2.4 Indoor Units Capacity For 24000BTU Capacity Model 24000BTU TAS-24EH 5.2.4.1 Cooling Capacity (BTU)---Run Model,230V,Indoor fan at high speed INDOOR ENTERING AIR DB/WB TEMPERATURE [ OUTDOOR ENTERING AIR DB TEMPERATURE[0F] DATA 72/59...
  • Page 18 5.2.4.2 Heating Capacity (BTU)---Run Model,230V,Indoor fan at high speed ID COIL ENTERING AIR DB TEMPERATURE [ OD COILENTERING AIR DB/WB TEM DATA PERATU RE[ 15680 14455 13475 1.35 1.49 1.63 17395 16170 15190 14/10 1.63 1.76 1.93 18620 17640 16415 20/18 1.85 1.98...
  • Page 19 Heating Capacity Ratio Vs. Outdoor Temperature Heating Capacity Correction Factor Outdoor Temp.(deg F) Capacity Correction Factor Due to Tubing Length (One Way) 5.3.1 Indoor units Model TAS-09MVH TAS-12MVH TAS-09EH TAS-12EH TAS-18EH TAS-24EH 5.3.1.1 Cooling 5.3.1.2 Heating SERVICE MANUAL FOR AMERICA...
  • Page 20: Pressure Curves

    6. Pressure Curve Model TAS-09EH/O TAS-18MVH/O TAS-12EH/O TAS-24MVH/O TAS-18EH/O TAS-24EH/O 6.1.1 Suction Pressure Curve 6.1.2 Discharge Pressure Curve SERVICE MANUAL FOR AMERICA...
  • Page 21: Electrical Data

    E L E C T R I C A L D A T A Model TAS-09EH/O Power Supply 1 PH, 115 VAC,60Hz Connected to Outdoor Maximum Current 9.3A Inrush Current Starting Current Circuit breaker Power supply wiring - No. x cross section 1 X 3 X 2.5 mm...
  • Page 22 Power supply wiring - No. x cross section 1 X 3 X 2.5 mm 2 X 4 X 1 mm Interconnecting cable - No. x cross section Model TAS-24EH/O Power Supply 1 PH, 230 VAC,60Hz Connected to Outdoor Maximum Current 12.2A Inrush Current Starting Current...
  • Page 23: Wiring Diagrams

    W I R I N G D I A G R A M S 8 . 1 T A S - 0 9 E H / O W i r i n g D i a g r a m 8 .
  • Page 24 8 . 3 T A S - 1 8 E H / O W i r i n g D i a g r a m 8 . 4 T A S - 2 4 E H / O W i r i n g D i a g r a m 8 .
  • Page 25 8 . 6 T A S - 2 4 M V H / O W i r i n g D i a g r a m 8 . 4 T A S - 1 8 M V H / O T A S - 2 4 M V H / O I n d o o r - O u t d o o r W i r i n g D i a g r a m SERVICE MANUAL FOR AMERICA...
  • Page 26: Refrigeration Diagrams

    8 . 5 T A S - 0 9 E H / O T A S - 1 2 E H / O T A S - 1 8 E H / O T A S - 2 4 E H / O I n d o o r - O u t d o o r W i r i n g D i a g r a m REFRIGERATION DIAGRAMS SERVICE MANUAL FOR AMERICA...
  • Page 27 9 . 1 T A S - 0 9 E H / O R e f r i g e r a t i o n D i a g r a m 9 . 2 T A S - 1 2 E H / O R e f r i g e r a t i o n D i a g r a m 9 .
  • Page 28 9 . 4 T A S - 1 8 M V H / O R e f r i g e r a t i o n D i a g r a m 9 . 5 T A S - 2 4 M V H / O R e f r i g e r a t i o n D i a g r a m SERVICE MANUAL FOR AMERICA...
  • Page 29: Tubing Connections

    1 0 . T U B I N G C O N N E C T I O N S SERVICE MANUAL FOR AMERICA...
  • Page 30: Control System

    T U B E ( I n c h ) ¼ ” ~ ” ½ ” ~ ” ¾ ” T O R Q U E ( N m ) 11-13 40-45 60-65 70-75 80-85 F l a r e N u t s 13-20 13-20 18-25...
  • Page 31 Function of Inverter indoor unit 一、summary 1. This control is use for DC Multi-Spilt air conditioners. 2. Power of indoor unit supply is 220-240V/50Hz, voltage range is 170V~270V. 3. Control precision of indoor temperature is ±1.8 4. Indoor fan motor is PG motor. 5.
  • Page 32  five running modes Auto, cooling, heating, dehumidify, ventilation.  Timer function  Indoor temperature detect.  Indoor coil temperature detect.  Indoor fan speed control cooling: turbo/high speed/middle speed/low speed/ lower speed heating: turbo/high speed/middle speed/low speed/ lower speed ...
  • Page 33 speed Heating 1300 1150 speed DC Inverter 1:2 PG motor speed: 12000BTU: mode higher high middle lower Cooling 1250 1200 speed Heating 1250 1200 speed 9000BTU: mode higher high middle lower Cooling 1250 1150 speed Heating 1250 1150 speed 四、operating mode Air conditioner have four operating mode: auto, cooling, dehumidify, heating.
  • Page 34  The indoor blower fan is running at low speed and it can’t change.  Air conditioner haven’t turbo and economic function in dehumidify mode.  Flap position: flap at 85 degree position and it can’t change.  It require indoor unit to reduce power if indoor room temp. continuous less than or equal to 15 degree for 5 minutes, when room temp.
  • Page 35  Turn off air conditioner in heating mode, if the coil pipe temp. of indoor unit is more than 104 F, indoor blower fan is running at low speed. If the coil pipe temp. of indoor unit is less than or equal to 104 F or turn off air conditioner over 2 minutes, It shutdown indoor blower fan.
  • Page 36 Full open Fixed Full close  Power on, flap run to full close position.  Turn off air conditioner, flap run to full close position.  Turn on air conditioner, flap first run to full open position, then run to correspond position. ...
  • Page 37: Other Function

     If no feedback signal continuous 30 seconds during PG motor running, it turn off air conditioner and display fan motor error. 4. Communicate fault  If it can’t receive correct signals after air conditioner has run for 60 seconds, it turn off air conditioner and display communicate error.
  • Page 38 1、Cooling Condition Entering Method label Capacity Pressing Tubro for 5 times+Setting temp.77 Pressing Tubro for 5 times+Setting temp.75 Pressing Tubro for 5 times+Setting temp.73 Pressing Tubro for 5 times+Setting temp.71 Pressing Tubro for 5 times+Setting temp.69 Pressing Tubro for 5 times+Setting temp.67 A2:Indoor temp.
  • Page 39 一. System Frame Drawing everse Valve(Current in cooling condition ) Condenser of Outdoor Unit Temperature of the Middle of Outdoor Coils Temperature of Exhaust Expansion Valve 1 Expansion Valve 2 Temperature of suction Compressor Liquid Tank Evaporator 1 of Indoor Unit Ambient Temperature of Indoor 1 Ambient Temperature of Outdoor Evaporator 2 of Indoor Unit...
  • Page 40 Control of Expansion Valve in Cooling Mode 1. Reset of Expansion Valve In the first time ,the expansion valves in all channels shall be shut down 600 steps, then the expansion valve corresponding to the indoor unit in normal communications with the outdoor unit shall be opened to standby mode steps.
  • Page 41 outdoor FM figure 3 五 .Operation in Dehumidify Mode Dehumidify mode is same as cooling mode. 六 .Operation in heating Mode Adjustment of Expansion Valve: 1.Reset of Expansion Valve In the first time,the expansion valves in two channels shall be shut down 600 steps, then the expansion valve corresponding to the indoor unit in normal communications with the outdoor unit shall be opened to standby mode steps.
  • Page 42 outdoor FM reverse valve figure 5 七.Defrost of heating mode(figure 6) 1. Defrost start condition F,it can’t defrost. When the time of defrost If outdoor ambient is more than or equal to 61 interval is end , outdoor coil pipe temp. and outdoor ambient temp. continuous meet all conditions for 5 minutes, it enter defrost process: 1) If outdoor ambient temp.
  • Page 43 八.Control of oil return circle 1. Oil return circle period When air conditioner has run for 10 minutes or accumulate time T is end, it execute oil return msro circle once. When compressor is running to oil return circle, the indoor unit which have communication is return oil, expand valve is open fully and compressor’s frequency increase more than 3/5 of max frequency for 90 seconds, the expand valve of indoor unit which no communication is close.
  • Page 44 4. Leakage or reverse valve fault The air conditioner shutdown immediately when meet one of below conditions. 1) Heating: coil pipe temp. of outdoor unit can’t decrease 3 degree within setting time and coil pipe temp. of indoor unit can’t increase 3 degree all along. 2) Cooling: coil pipe temp.
  • Page 45 1) The air conditioner stop running immediately and display error code when input current more than or equal to Imax. 2) The compressor decrease 2Hz per 3 seconds until input current less than or equal to (Imax-13) when the input current more than (Imax-13). 2)The compressor decrease 1Hz per 3 seconds until input current less than or equal to (Imax-16) when the input current more than (Imax-16).
  • Page 46: 12. Troubleshooting

    12. TROUBLESHOOTING WARNING!!! When Power Up – the whole outdoor unit controller, including the wiring, is under HIGH VOLTAGE!!! Never open the Outdoor unit before turning off the Power!!! When turned off, the system is still charged (400V)!!! It takes about 3 Min. to discharge the system. Touching the controller before discharging may cause an electrical shock!!! For safe handling of the controller please refer to section 1.6 below.
  • Page 47 1: discharge temp. too high.---maybe leak refrigerant, add refrigerant. 2:outdoor ambient temp. too high, if (T<-4 F,T>131 F), it will alarm. 3:temp. switch of compressor cut off.。 4:Communication interfere. (earth wire can’t with communicate wire in same cable)---check cable. P7: 1,PFC board fault.---change PFC board.
  • Page 48 1 3 . E X P L O D E D V I E W S A N D S P A R E P A R T S L I S T S 13.1 outdoor unit : TAS-09EH/O description name number NO.
  • Page 49 13.2 outdoor unit : TAS-12EH/O description name number NO. description name number 顶盖板 Top panel 高压阀 High-pressure valve 电控盒 Electric box 压缩机 Compressor 背网 Rear Grill 底盘 Base 中隔板 Partition board 冷凝器 Condenser 四通阀 Four-way valve 电机支架 Motor support 电子膨胀阀 Electronic expansion valve 电机...
  • Page 50 13.3 outdoor unit : TAS-18EH/O NO. description name number NO. description name number 四通阀组 前网罩 Front Grill Four-way valve assembly 件 电子膨胀 面 板 Front Plate Electronic expansion valve 阀 轴流风轮 Axial flow fan 右侧板 Right panel 电 机 Motor 电器盒盖...
  • Page 51 13.4 outdoor unit : TAS-24EH/O description name number NO. description name number 顶盖板 Top panel 维修板 Maintenance plate 减振块 Anti-vibration pad 小抽手 Small handle 中隔板 Partition board 压缩机 Compressor 电控盒 Electric box 底盘 Base 四通阀 Four-way valve 冷凝器 Condenser 干燥过滤器 Desiccation filter 电机支架...
  • Page 52 13.5 outdoor unit : TAS-18MVH/O description name number NO. description name number 前网罩 Front Grill 电器盒盖 Top of the Electric Box 面 板 Front Plate 阀座板 Valve installation plate 轴流风轮 Axial flow fan A 机 DN4 截止阀 DN4 valve 左侧板 Left panel A 机...
  • Page 53 13.6 outdoor unit : TAS-24MVH/O description name number description name number 前网罩 Front Grill 电器盒盖 Top of the Electric Box 面 板 Front Plate 阀座板 Valve installation plate 轴流风轮 Axial flow fan A 机 DN4 截止阀 DN4 valve 左护网 Left protect net A 机...
  • Page 54 APPENDIX A APPENDIX A INSTALLATION AND OPERATION MANUAL  I N S T A L L A T I O N M A N U A L C M V SERVICE MANUAL FOR AMERICA...
  • Page 55 F o r e w o r d This instruction Manual is the universal-purpose version for the models of separate wall-mounted air conditioners manufactured by our Co. The appearance of the units that you purchase might be s l i ght l y d i f f e r e n t from the ones described in the Manual, but it does not affect your proper operations and usage.
  • Page 56 within the indoor unit packa 1 LOCATION OF OUTDOOR UNIT Select the location considering the following: O U T D O O R U N I T 1 .The location must allow easy servicing and provide good air circulation as shown in fig2. 2.The unit may be suspended from a wall by a bracked(Optional)or located in a free standing position on the floor(preferably slightly elevated).
  • Page 57 2 ELECTRICAL CONNECTION BETWEEN OUTDOOR AND INDOOR UNIT ELECTRICAL REQUIREMENTS Electrical wiring and connections should be made by qualified electricians and in accordance with local electrical codes and regulation.The air conditioner units must be grounded. The air conditioner units must be connected to an adequate power outlet from a separate branch circuit protected by a time delay circuit breaker,as specified on unit's nameplate.
  • Page 58 3 INSTALLATION/SERVICE TOOLS (ONLY FOR R410A PRODUCT) C A U T I O N New Refrigerant Air Conditioner Installation This air conditioner adopts the new HFC refrigerant (R410A) which does not destroy ozone layer. R410A refrigerant is approx . 1.6 times of refigerant R22. Accompanied with the adoption of the new refrigerant , the refrigeration machine oil has also been changed.
  • Page 59 By incressing the clamp bar'receiving hole Flare tool size , strength of spring in the tool has been (clutch type) improved. Gauge for projection Used when flare is made by using conventional adjustment flare tool. Connected to conventional vacuum pump,it is necessary to use an adapter to prevent vacuum pump oil from flowing back into the charge Vacuum pump adapter...
  • Page 60: Refrigerant Tubing

    4 REFRIGERANT TUBING CONNECT THE INDOOR TO THE OUTDOOR UNIT The indoor unit contains a small quantity of nitrogen.Do not unscrew the nuts from the unit until you are ready to connect the tubing.The outdoor unit is supplied with suffcient refrigerant charge(R410A). Refer to outdoor unit nameplate.
  • Page 61 Tightening torques of unions and valve caops: TUBE SIZE TORQUE Liquid line 1/4" 1 5 - 2 0 N.M. Suction line 3/8" 3 0 - 3 5 N.M. Suction line 1/2" 5 0 - 5 4 N.M. Suction line 5/8" 7 5 - 7 8 N.M.
  • Page 62 1 .Charging set 5.Cap 9.Liquid valve 2.Vacuum pump 6.Suction valve 10.INDOOR UNIT 3.OUTDOOR UNIT 7.Service valve 1 1.Suction flare connection 4.Service valve 8.Cap 12.Liquid flare connection 5 FINAL TASKS 1 .Check all valve caps and ensure that they had tightened properly.Close the valve cover. 2.Fill gaps on the wall between hole sides and tubing with sealer.