2)Select the suspension bolt locations and the
pipe hole location.
·
Place the left hanger bracket on the nuts
and washers of the suspension bolts.
·
Make sure that the left hanger bracket has
been fixed on the nuts and washers securely,
install the right hanger bracket suspension
hook on the nuts and washers.
(When installing the indoor unit, you can
slightly remove the suspension bolts.)
3).Fix with 4 suspension bolts,which can endure load
of 530N.
4).Check the measurements the length of the
suspension bolts.
5).Fasten the hanging plate onto the suspension
bolts.
6).Install the unit to the hanging plate.
i.Slide the unit from front side to get it hanged on the
hanging plate
with bolts.
ii.Fasten the four fixing bolts(M8:2each on the left
and right sides)firmly.
iii.Fasten the two screws(M5:1 each on the left and
right sides.)
Hanging plate
ceiling
Hanging plate
Suspension bolt
Fig. 3.3.8
strew for hanging
plate(M5)
Fig. 3.3.9
Installation and Maintenance
Floor standing type installation
1)Select the suspension bolt locations and the
pipe hole location.
i
.Use enclosed paper pattern as a reference ,and drill
the holes for the suspension bolts and pipe.
Note:Decide the locations based on the direct
measurements.
ii.Once the locations are properly placed, the paper
pattern can be removed.
Wall
Floor
Fig. 3.3.10
2).Fix with 4 suspension bolts,and fasten the four
fixing bolts(M8:2each on the left and right
sides)firmly.
3).Fasten the two screws of Air Intake Grille(M5:1
each on the left and right sides).
3.3.5 The horizon adjustment of the indoor unit
(1) Make sure that the hanger bracket is fixed by the
nut and the washer.
(2) Adjust the height of the unit.
(3) Check the unit is horizontally level.
*To ensure smooth drain flow,install the unit with a
descending slope(0-3mm) toward the drain outlet.
(4) After the adjustment, tighten the nut and swear the
thread locker on the suspension to prevent the nuts
from loosening.
CAUTION
(1) During the installation, please cover the unit with the
plastic cloth to keep it clean.
(2) Make sure the unit is installed level using a level or
a plastic tube filled with water in using a plastic tube
instead of a level, adjust the top surface of the unit to
the surface of the water at both ends of the plastic tube
and adjust the unit horizontally.(one thing to watch out
for in particular is if it is installed so that the slope is not
in the direction of the drain piping, as this might cause
leaking.)