Panasonic S-22KA1E5 Service Manual page 133

Hide thumbs Also See for S-22KA1E5:
Table of Contents

Advertisement

■ Automatic setting
By switching ON the indoor unit's power supply with the DIP switch where the A/C No. is set to "01" (factory
setting), the A/C No. will be automatically set. (After activating the power for all indoor units, the automatic
setting takes approximately one minute.)
Once the A/C No. is automatically set, even when the power supply is switched OFF, the setting is stored.
To view the resetting result, follow the instructions for the "group control automatic address reset". Refer to
the item "On-site setting" in the installation instruction manual that comes with the wired controller for the
"group control automatic address reset" method.
* If the indoor unit's A/C No. DIP switch is not set to "01", the automatic setting cannot be reset.
■ Manual setting
The manual setting is performed using each indoor unit's printed circuit board DIP switch. (Refer to the
diagram below)
Set the DIP switch once the power supply for each indoor unit is switched OFF. When the power supply is
turned ON, the stored A/C No. is recalled.
To change the setting of the A/C No., turn OFF the power supply before resetting the DIP switch.
* Ensure that there is no redundancy in the A/C No. Any redundancy can cause faulty control.
* Ensure to set the A/C No. to "01" for 1 indoor unit.
A/C No.
Indoor unit
printed circuit
board DIP switch
(SW2)
Unnecessary
operation
A/C No.
Indoor unit printed
circuit board DIP
switch (SW2)
(Refer to the remote controller's installation instruction manual for the remote controller settings.)
11.9.9
AS FOR TIMER OUTPUT
Connect the timer cord to connector (CN-TIMER) on print circuit board.
Timer setting
The connector must use XH-2 (housing) manufactured by J.S.T. Mfg. Co., Ltd.
Wiring must use vinyl code with the sheath or cable line diameter 0.3mm
The length of wiring should be within 150m and separated from power line in order to prevent malfunction.
The input current is DC5V, and 1mA. The relay contact must use the contact for the minute electric current
suitable for this.
01
02
03
1-ON
2-ON
09
10
11
4-ON
1,4-ON
2,4-ON
CN-TIMER
Printed
2
circuit
board
1
Connector
04
05
1,2-ON
3-ON
12
13
1,2,4-ON
3,4-ON
Contact
Relay contact
Close: RUN
Open: STOP
Timer
d.c. 5V
133
06
07
08
1,3-ON
2,3-ON
1,2,3-ON
14
15
16
1,3,4-ON
2,3,4-ON
1,2,3,4-ON
2
.