Panasonic S-22KA1E5 Service Manual page 118

Hide thumbs Also See for S-22KA1E5:
Table of Contents

Advertisement

Carry out Earthing work.
Do not connect the Earth return to the gas pipe, water line pipe, lightning rod and telephone lines.
Imperfection in Earth return may lead to electric shock.
Do not install the unit at the place where the possibility of inflammable gas leakage exists. If gas leakage should arise and the gas builds
up around the unit, such situation may lead to ignition.
Mounting of the earth leakage circuit breaker is required. Omission in mounting of the earth leakage circuit breaker may lead to electric
shock.
Drain piping should be made to ensure secure drainage according to the manual for installation work and carry out the thermal insulation
to prevent the occurrence of condensation.
Imperfection in piping work leads to water leakage and may cause the house and property, etc. to become wet.
Position the indoor unit, outdoor unit, power cords and indoor/outdoor unit connection cables in a way so that they are at least 1 meter
away from televisions and radios. This is to avoid problems such as interference with picture and/or sound. (However, note that
depending on the electromagnetic wave conditions, interference may still occur even if the separation distance is more than 1 meter.)
11.8.1
ACCESSORIES PACKED IN THE INDOOR UNIT CONTAINER
Name
Drain hose
Heat insulator
Band
Flat washer for M10
Installation Instruction
11.8.2
SELECTING THE LOCATION FOR THE INDOOR UNIT
Provide a check port on the piping side ceiling for repair and maintenance.
Install the indoor unit once the following conditions are satisfied and after receiving the customer approval.
1. The indoor unit must be within a maintenance space.
2. The indoor unit must be free from any obstacles in path of the air inlet and outlet, and must allow spreading
of air throughout the room.
(Unit: mm)
✳ If the height from the floor to ceiling exceeds three meters, air flow distribution deteriorates and the effect is
decreased.
3. The installation position must be able to support a load four times the indoor unit weight.
4. The indoor unit must be away from heat and steam sources, but avoid installing it near an entrance.
5. The indoor unit must allow easy draining.
6. The indoor unit must allow easy connection to the outdoor unit.
7. Place the indoor unit easy water drainage. (Suitable dimension "H" is necessary to get slop to drain as figure.)
8. The indoor unit must be from at least 3m away from any noise-generating equipment. The electrical wiring
should be locally decided.
9. If the power supply is subject to noise generation, add a suppressor.
10. Do not install the indoor unit in a laundry. Electric shocks may result.
Q'ty
Appearance
1
2
4
8
1
[Top view]
Inspection hole
Control box
Air conditioner
600
Front
Cautions
For drain piping
For insulating refrigerant pipe joint
For fastening the heat insulator
For fixing the hanging bolts
This manual
600
Warnings
118