6 Type Tests
6.1 IEC 61850-3 Type Tests
Test
IEC 61000-4-2
ESD
IEC 61000-4-3
Radiated RFI
Burst (Fast
IEC 61000-4-4
Transient)
IEC 61000-4-5
Surge
Induced
IEC 61000-4-6
(Conducted) RFI
IEC 61000-4-8
Magnetic Field
IEC 61000-4-29
Voltage Dips &
Interrupts
IEC 61000-4-11
Damped
IEC 61000-4-12
Oscillatory
Mains Frequency
IEC 61000-4-16
Voltage
Ripple on D.C.
IEC 61000-4-17
Power Supply
Dielectric
IEC 60255-5
Strength
IEC 60255-5
H.V. Impulse
Table 13 - IEC 61850-3 Type Tests
©
2007 RuggedCom Inc. All rights reserved
Description
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
D.C. Power ports
A.C. Power ports
Earth ground ports
Signal ports
D.C. Power ports
A.C. Power ports
Signal ports
D.C Power ports
A.C. Power ports
Earth ground ports
Enclosure ports
D.C. Power ports
A.C. Power ports
Signal ports
D.C. Power ports
A.C. Power ports
Signal ports
D.C. Power ports
D.C. Power ports
Signal ports
D.C. Power ports
A.C. Power ports
Signal ports
D.C. Power ports
A.C. Power ports
25
Test Levels
+/- 8kV
+/- 15kV
20 V/m
+/- 4kV @ 2.5kHz
+/- 4kV
+/- 4kV
+/- 4kV
+/- 4kV line-to-earth, +/- 2kV line-to-
line
+/- 2kV line-to-earth, +/- 1kV line-to-
line
+/- 4kV line-to-earth, +/- 2kV line-to-
line
10V
10V
10V
10V
40 A/m continuous, 1000 A/m for 1 s
30% for 0.1s, 60% for 0.1s, 100% for
0.05s
30% for 1 period, 60% for 50 periods
100% for 5 periods, 100% for 50
periods
2
2.5kV common, 1kV differential mode
@ 1MHz
2.5kV common, 1kV differential mode
@ 1MHz
2.5kV common, 1kV differential mode
@ 1MHz
30V Continuous, 300V for 1s
30V Continuous, 300V for 1s
10%
2kVac (Fail-Safe Relay output)
2kVac
2kVac
5kV (Fail-Safe Relay output)
5kV
5kV
Severity
Levels
4
4
x
x
4
4
4
4
3
4
3
3
3
3
N/A
N/A
N/A
N/A
3
3
3
4
4
3
N/A
N/A
N/A
N/A
N/A
N/A
Rev100
Need help?
Do you have a question about the RuggedServer RS910 and is the answer not in the manual?