CAUTION
Taping the fl are nuts
Wind the white insulation tape around the flare nuts at the
gas tube connections. Then cover up the tubing connections
with the flare insulator, and fill the gap at the union with the
supplied black insulation tape. Finally, fasten the insulator at
both ends with the supplied vinyl clamps. (Fig. 5-8)
Insulation material
The material used for insulation must have good insulation
characteristics, be easy to use, be age resistant, and must not
easily absorb moisture.
CAUTION
o41.28
100
90
Thickness
80
30mm
Thickness
70
20mm
60
Thickness
50
10mm
40
40
50
10
20
Ambient temperature [°C]
If the exterior of the outdoor
unit valves has been fi nished
with a square duct covering,
make sure you allow suffi cient
space to use the valves and
to allow the panels to be
attached and removed.
After a tube has been
insulated, never try to bend it
into a narrow curve because
it can cause the tube to break
or crack.
Thickness
30mm
Thickness
20mm
Thickness
10mm
30
40
50
Sealer (supplied)
Unit side
insulator
Flare nut
Drain insulator
and clamp. Large
(supplied)
Packing
clamp. Small
hose band
(supplied)
Never grasp the drain or refrigerant connecting outlets
when moving the unit.
34
Insulation tape (white)
(supplied)
Flare insulator (supplied)
Tube insulator
(not supplied)
Heat resistant
120°C or above
Vinyl clamps (supplied)
Fig. 5-8
Refrigerant tubing and insulator
(not supplied)
Drain pipe and insulator
(not supplied)
Insulation
tape
Vinyl
clamp
Flare
insulator
Seal
The procedure used for
installing the insulator
for both gas and liquid
tubes is the same.
Fig. 5-9