Potterton Profile Installation And Servicing Instructions page 6

100e, fanned balanced flue gas fired boiler

Advertisement

REAR OR SIDE FLUEING - Page 6
FIG. 4 FLUE LENGTHS
ELECTRICITY SUPPLY
A 240 volts ~ 50Hz, single phase electricity supply
fused to 3 amperes, must be provided in accordance
with the latest edition of the I.E.E. Wiring Regulations
and any other local regulations that may apply. The
current rating of the wiring to the boiler must exceed 3
amperes and have a cross sectional area of at least
2
0.75mm
in accordance with BS 6500. Table 16.
TECHNICAL DATA - Page 6
Maximum working head
Minimum working head on
Fully Pumped systems
Minimum circulating head
on Gravity systems
Gas supply pressure
Maximum Flow temperature
Electricity supply
Internal Fuse
Supplied By www.heating spares.co Tel. 0161 620 6677
30.5m (100 ft)
305mm (1 ft)
1.2m (4 ft)
20mbar
º
82
C
240v ~ 50Hz fused
at 3A
T1A
6
STANDARD FLUE
SYSTEM
1 METRE FLUE
SYSTEM
The supply to the boiler and its associated
equipment should be controlled by a 3A fused
double pole switch (having at least 3mm contact
separation in both poles) so that complete isolation
from the supply can be achieved to enable servicing
work to be carried out in safety.
Power consumption
(excluding pump)
Flow/Return connection
Gas supply connection
Water Content
Appliance Weight-installed
Appliance Weight-lift
MAXIMUM
LENGTH 'X'
510mm
(20in)
955mm
(37in)
80 watts
28mm copper
Rc. 1/2 (1/2 in BSP
Female)
6.5 litre (1.43 gal)
63.5kg (140 Ibs)
54.5kg (120 Ibs)