8. Electric Characteristics

Model
Hz
YOCA 12
YOHA 12
YOCA 18
YOHA 18
YOCA 24
YOHA 24
YOCA 36
50
YOHA 36
YOCA 36
YOHA 36
YOCA 48
YOHA 48
YOCA 60
YOHA 60
Symbols:
MCA: Min. Circuit Amps.
MFA: Max. Fuse Amps..
FLA: Full Load Amps.
Kw: Rate Motor Output
Notes:
3. Voltage range should not over the value of above table.
4. Maximum allowable voltage variation between phase is 2%
5. Selection wire size based on the larger value of MCA.
6. MCA/MFA
MCA = 1.25 × FLA
MFA ≤ 4 × FLA
(Next lower standard fuse rating min. 15A)
5. Instead of fuse, circuit breaker is also acceptable.
Indoor Units
Voltage
Min.
Max.
220~240
198
264
380
342
418
Power Supply
Indoor fan motor
MCA
MFA
kW
7.6
15
0.03
7.6
15
0.03
10.6
20
0.055
11.0
20
0.055
17.6
50
0.055
17.0
50
0.055
22.5
70
0.08
22.0
70
0.08
8.9
20
0.08
8.2
20
0.08
10.6
30
0.12
10.3
30
0.12
12.5
30
0.12
12.5
30
0.12
Power input(W)
FLA
Cooling
Heating
0.145
1370
0.145
1370
0.52
1900
0.52
1900
0.52
3100
0.52
2800
0.59
4050
0.59
3700
0.59
4050
0.59
3700
0.78
4800
0.78
4700
0.78
6570
0.78
6570
1350
1850
2860
3350
3350
4900
6900