5. Electronic Function

5.1 Abbreviation

T1: Indoor ambient temperature
T2: Middle indoor heat exchanger coil
temperature
T2B: Indoor heat exchanger exhaust coil
temperature (located on the outdoor unit)
T3: Outdoor heat exchanger pipe temperature
T4: Outdoor ambient temperature
T5: Compressor discharge temperature

5.2 Electric Control Working Environment.

5.2.1 Input voltage: 230V.
5.2.2 Input power frequency: 60Hz.
5.2.3 Indoor fan standard working amp.: <1A
5.2.4 Outdoor fan standard working amp.: <1.5A.
5.2.5 Four-way valve standard amp.: <1A.

5.3 Main Protection

5.3.1 Compressor Restart Delay
---- The compressor takes 1 minute to start up the
first time. Further restarts take 3 minutes.
5.3.2 Temperature Protection of Compressor
Discharge.
When
the
discharge
compressor rises, the running frequency is limited
according to the following rules:
(221 ℉
----If
105
maintain the current frequency.
----If the temperature increase and T5≧ 110℃
℉), decrease the frequency to a lower level
(230
every 2 minutes till to F1.
---If T5 ≧ 115 ℃
(239 ℉
compressor stops and then restart untill T5<90℃
(194 ℉).
5.3.3 Fan Speed Malfunction
temperature
of
) ≦
℃ (230 ℉ ),
T5<110
) for 10 seconds, the
---- If outdoor fan speed is lower than
higher than 2400RPM for 60 seconds or more,
the unit stops and LED displays
5.3.4 Inverter Module Protection.
---- The inverter protection module ensures that
faults related to current, voltage, or temperature
does not damage the inverter.
If these protections are triggered, the A/C unit
stops and the LED displays the failure code.
The unit restarts 3 minutes after the protection
mechanism has turned off.
5.3.5 Low Voltage Protection
V O L T A G E
Note: If low voltage protection triggers and
voltage is not restored to normal within 3
minutes, the protection remains active even
after a machine restart.
5.3.6 Compressor Current Limit Protection
The temperature interval for the current limit is
the same as the range of the T4 frequency limit.
the
Cooling mode:
16
100RPM
failure code.
E8
N o lim it
V O L T _ LT M _ F R E Q 1_ A D D
V O L T _ LT M _ F R E Q 2 _ A D D