Indoor Unit; Function Of Dip Switch - Mitsubishi Electric PKFY-P63VFM-E Technical & Service Manual

Pkfy series wall mounted r410a/r407c/r22 split-type, heat pump air conditioners
Table of Contents

Advertisement

7-2. FUNCTION OF DIP SWITCH

PKFY-P63VFM-E
PKFY-P100VFM-E
Switch Pole
Function
Thermistor<Intake temperature
1
detection>position
2
Filter clogging detection
3
Filter cleaning sign
4
Air intake
SW1
5
Remote indication switching
Mode
6
Humidifier control
Selection
7
Air flow set in case of
8
Heat thermostat OFF
9
Auto restart
10
Power source ON/OFF
SW2
MODELS
Capacity
1~6
PKFY-
code
P63VFM-E
setting
1
Heat pump/Cooling only
2
Louver
3
Vane
4
Vane swing function
SW3
5
Vane horizontal angle
Function
Vane cooling limit angle setting w4 Horizontal angle
6
Selection
Indoor linear expansion
7
valve opening
8
Heater 4degrees up
Target Superheat setting w5 9degrees
9
10
Target Sub cool setting
SW4
Unit
1~5
Selection
ON
Built-in remote controller
Provided
2500hr
Effective
Thermostat ON signal indication Fan output indication
Always operated while
the heating mode
Fix to LOW
Depends on setting
remote controller
Effective
Effective
SW2
MODELS
ON
ON
PKFY-
OFF
OFF
P100VFM-E
1 2 3 4 5 6
Cooling only model
Available
Available
Available
Second setting
Effective
Not effective
15degrees
ON
OFF
1 2 3 4 5
Operation by switch
OFF

Indoor unit

Not provided
100hr
Not effective
Operated depends
w1
on the condition
w3 Fix to EXTRA LOW
w3 Depends on SW1-7
Not effective
Not effective
SW2
1 2 3 4 5 6
Heat pump model
Not available
Not available
Not available
First setting
Down B,C
Not effective
Effective
6degrees
10degrees
18
Remarks
Address board
<At delivery>
ON
OFF
1 2 3 4 5 6 7 8 9 10
NOTE:
w1 At Heating mode, fan
operating.
w2 At Heating mode, operat-
ing heat thermostat ON.
w2
w3 SW1-7=OFF, SW1-8=ON
Setting air flow.
w3
SW1-7=ON, SW1-8=ON
Indoor fan stop.
Indoor controller board
Set while the unit is off.
<At delivery>
Set for each capacity.
Indoor controller board
Set while the unit is off.
<At delivery>
ON
OFF
1 2 3 4 5 6 7 8 9 10
NOTE:
w4 At cooling mode, each
angle can be used only 1
hour.
w5 sw3-9 setting
PKFY-P63VFM-E = ON
PKFY-P100VFM-E = OFF
Indoor controller board
Set while the unit is off.
<At delivery>
ON
OFF
1 2 3 4 5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pkfy-p100vfm-e pkfy-p100vfm-e

Table of Contents