Air conditioners for building application indoor unit
Table of Contents

Advertisement

Available languages

Available languages

2. Installation location

 PKFY-WL·NKMU-E
B
L
F
G

3. Installing the indoor unit

1
2
4
5
7
8
 PKFY-WL·NKMU-E
H
F
15.5 (39/64)
0
25 (63/64)
50 (1-31/32)
75 (2-61/64)
100 (3-15/16)
117 (3-39/64)
125 (4-59/64)
142 (5-39/32)
192 (7-9/16)
242 (9-17/32)
279.5 (11)
C
K
en
A
C
D
2
1170
A
46-1/16
C K
D
E
*
H
Fig. 2-1
3
6
9
Fig. 3-1
G A
E
150 (5-29/32)
A
I
J
Fig. 3-2
A
Sleeve
B
B
Hole
C
(Indoors)
D
Wall
E
E
(Outdoors)
Fig. 3-3
2.1. Outline dimensions (Indoor unit) (Fig. 2-1)
Select a proper position allowing the following clearances for installation and
(mm)
maintenance.
(inch)
 PKFY-WL·NKMU-E
A
Min. 100.5
Min. 3-31/32
F
Air outlet: Do not place an obstacle within 1500 mm, 59-1/16 inch of the air outlet.
G
Floor surface
H
Furnishing
J
I
When the projection dimension of a curtain rail or the like from the wall exceeds 60 mm,
I
2-23/64 inch extra distance should be taken because the fan air current may create a short
cycle.
J
1800 mm, 70-7/8 inch or greater from the floor surface (for high location mounting)
K
108 mm, 4-1/4 inch or greater with left or rear left piping
L
Minimum 7 mm, 9/32 inch
3.1. Check the indoor unit accessories (Fig. 3-1)
The indoor unit should be supplied with the following accessories.
PART
NUMBER
1
Mount board
2
Tapping screw 4 × 25
3
Felt tape
4
Band
5
D-pipe
6
F-pipe
7
G-pipe
8
H-pipe
9
Insulation (3×80×130)(mm)
3.2. Installing the wall mounting fixture
3.2.1. Setting the wall mounting fixture and piping positions
► Using the wall mounting fixture, determine the unit's installation position
and the locations of the piping holes to be drilled.
mm (inch)
Warning:
Before drilling a hole in the wall, you must consult the building contractor.
 PKFY-WL·NKMU-E (Fig. 3-2)
B
54 (2-1/8)
32 (1-17/64)
A
Mount board
25 (63/64)
12.5 (31/64)
B
0
Indoor unit
12.5 (31/64)
37.5 (1-15/32)
C
Bottom left rear pipe hole (ø75-ø80 mm, 2-61/64~3-5/32 inch)
62.5 (2-29/64)
87.5 (3-7/16)
104.5 (4-7/64)
D
Bottom right rear pipe hole (ø100 mm, 3-15/16 inch)
129.5 (5-3/32)
167 (6-37/64)
E
Knockout hole for left rear hole
217 (8-35/64)
229.5 (9-1/32)
F
Bolt hole (4-ø9 mm, 23/64 inch hole)
246 (9-11/16)
264 (10-25/64)
292 (11-1/2)
G
Center measurement hole (ø2.5 mm, 3/32 inch hole)
308.5 (12-9/64)
311 (12-1/4)
H
Tapping hole (75-ø5.1 mm, 13/64 inch hole)
D
I
Hole centre
J
Align the scale with the line.
K
Insert scale.
3.2.2. Drilling the piping hole (Fig. 3-3)
► Use a core drill to make a hole of 100 mm, 3-15/16 inch diameter in the wall
in the piping direction, at the position shown in the diagram to the left.
► The hole should incline so that the outside opening is lower than the
inside opening.
► Insert a sleeve (with a 100 mm, 3-15/16 inch diameter and purchased
locally) through the hole.
Note:
The purpose of the hole's inclination is to promote drain flow.
B
C
Min. 52.3
Min. 48
Min. 2-1/16
Min. 1-7/8
Min. 9-27/32
QUANTITY
ACCESSORY
WL18, WL24, WL30
1
7
2
4
1
1
2
1
4
1
(mm, inch)
D
E
Min. 250
Min. 220
Min. 8-21/32
LOCATION
OF
SETTING
Fix at the back