10.0 Changing Components – Page 21
Supplied By www.heating spares.co Tel. 0161 620 6677
10.3 Gas Tap, Igniter and FFD
NOTE: The tap incorporates a flow setting device on its
outlet connection. This is factory set and must not be
adjusted.
1.
Pull the electrode lead off the electrode (Fig. 45).
2.
Undo the thermocouple nut from the interrupter unit and
pull off the two leads (Fig. 46).
3.
Undo the pilot feed nut and the gas inlet and outlet nuts
from the tap assembly (Fig. 46).
4.
Note the orientation of all the pipes and remove them.
5.
Remove the gas tap (Fig. 46).
6.
Remove the interrupter unit from the gas tap (Fig. 46).
7.
Refit in reverse order of dismantling, ensuring that the
thermocouple nut is done up tight in the interrupter unit.
10.4 Injector (Fig. 47)
1.
Undo the screw retaining the injector cover to the
injector mounting plate and remove the cover.
2.
Undo the nut on the injector feed pipe at the injector.
3.
Remove the two screws securing the injector mounting
plate to the burner and undo the locknut retaining the
injector to the plate.
4.
Fit the new component and reassemble in reverse
order of dismantling.