Remote Controller Thermistor Abnormality - Daikin Super multi NX E Series Service Manual

Hide thumbs Also See for Super multi NX E Series:
Table of Contents

Advertisement

SiBE121135_A
6.7

Remote Controller Thermistor Abnormality

CJ
Error Code
Method of Error
Even if remote controller thermistor is faulty, system is possible to operate by system thermistor.
Malfunction detection is carried out by the temperature detected by remote controller thermistor.
Detection
Error Decision
The remote controller thermistor is disconnected or shorted while the unit is running.
Conditions
Supposed
Causes
Troubleshooting
Note:
To delete the record of error codes, press the [ON/OFF] button for 4 seconds or more while the
error code is displayed in the inspection mode.
Service Diagnosis
Defective thermistor
Broken wire
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Delete the record of error
codes. (See the Note.)
CJ
Is
displayed on the
remote controller
again?
NO
YES
Troubleshooting for SA Indoor Unit
Replace the remote
controller.
External factor other
than equipment
malfunction.
(for example, noise
etc.)
(R18062)
196