Problem Symptoms and Measures

2. Problem Symptoms and Measures

Problem Symptom
None of the units operates. Check the power supply.
Operation sometimes
stops.
Some indoor units do not
operate.
Heating operation is not
available.
Units operate but do not
cool, or do not heat.
Large operating noise and
vibrations
153
Check Item
Check the types of the indoor units.
Check the outdoor temperature.
Diagnose with remote controller
indication
Check the remote controller
addresses.
Check the power supply.
Check the outdoor temperature.
Diagnose with remote controller
indication.
Check the type of the indoor units.
Diagnose with remote controller
indication
Check the model type setting of the
remote controller.
Check for wiring and piping errors in
the connection between the indoor
and outdoor units.
Check for thermistor detection errors. Check if the thermistor is mounted securely.
Check for faulty operation of the
outdoor electronic expansion valve.
Diagnose with remote controller
indication.
Diagnose by service port pressure
and operating current.
Check the output voltage of the
power module.
Check the power module.
Check the installation condition.
Details of Measure
Check if the rated voltage is supplied.
Check if the indoor unit type is compatible with
the outdoor unit.
Heating operation cannot be used when the
outdoor temperature is 18°CWB or higher, and
cooling operation cannot be used when the
outdoor temperature is below –10 ~ 10°CDB
(depending on the model).
Check if address settings for the remote
controller and indoor unit are correct.
A power failure of 2 to 10 cycles can stop air
conditioner operation. (Operation lamp OFF)
Heating operation cannot be used when the
outdoor temperature is 18°CWB or higher, and
cooling operation cannot be used when the
outdoor temperature is below –10 ~ 10°CDB
(depending on the model).
Check if the indoor unit type is compatible with
the outdoor unit.
Make sure that the setting is for the heat pump
model type.
Conduct the wiring/piping error check described
on the product diagnosis nameplate.
Set all the units to cooling operation, and
compare the temperatures of the liquid pipes to
see if the each outdoor electronic expansion
valve works.
Check for refrigerant shortage.
Check if the required spaces for installation
(specified in the installation manual) are
provided.
SiBE121135_A
Reference
Page
167
253
167
167
253
167
200
240
Service Diagnosis