5.
USB Port to PC
This port allows connection and
communication from the USB port
on the computer to the UPS unit. The
UPS communicates its status to the
®
PowerPanel
Personal Edition
software. This interface is also
compatible with the UPS service
provided by Windows 98, Windows
ME, Windows NT, Windows 2000,
Windows XP, Windows Server
2003.
NOTE: Only one of these two ports
can be used as communication and
control of the UPS unit at one time.

Functional Test

AC Mode
The UPS delivers power to the loads derived from the utility and maintains proper battery charge. It also
regulates the output voltage to within a narrow range.
On-Battery Mode
The UPS operates on battery when the line voltage or frequency has fallen outside the limits. Local
users are alerted to this mode of operation by visual and audible indicators. The UPS provides power to
the load from the battery and through its inverter and the output voltage and frequency of the UPS are
regulated within a narrow range
1.
Switch On
Press the power switch on the front panel then the green LED will light up.
2.
Switch Off
Press again the power switch, the LED on the front panel will go off.
3.
Cold Start / Start on Battery:
This UPS can be turned on even when AC is not present.
Press the power switch on the front panel then the green LED will light up and flashing.
ROUTINE MAINTENANCE AND STORAGE
ROUTINE MAINTENANCE
1.
Use dry soft clothes to clean the front panel and plastic parts. Do not use any detergent that
contains alcoholic ingredient.
2.
The expected lifetime of the battery is around 3 years. Improper operation and harsh environment
will reduce the actual lifetime.
3.
Unplug the UPS from power inlet if the UPS will not operate for long period of time.
STORAGE
1.
First turn off your UPS and disconnect its power cord from the wall outlet. Disconnect all cables
connected the UPS to avoid battery drain.
2.
The UPS should be stored in a cool dry location.
3.
Make sure the battery is fully charged before the UPS is stored.
4.
For extended storage in moderate climates, the battery should be charged for 12 hours every 3
months by plugging the power cord into the wall receptacle and turning on the main switch. Repeat
it every 2 months in high temperature locations.
TROUBLE SHOOTING
Problem
Possible Cause
Batteries are not fully
The UPS does
charged.
not perform
expected
Battery is slightly worn out.
runtime.
The on/off switch is
designed to prevent
damage by rapidly turning it
off and on.
The unit is not connected to
The UPS will not
an AC outlet.
turn on.
The battery is worn out.
Mechanical problem.
Fuse is blown due to
overload
Outlets do not
provide power to
equipment
Batteries are discharged
Unit has been damaged by
a surge or spike.
®
PowerPanel
or
®
PowerPanel
The serial/USB cable is not
Personal Edition
connected.
is inactive (all
icons are gray).
The serial/USB cable is
connected to the wrong
port.
Solution
Recharge the battery by leaving the UPS
plugged in.
Contact CyberPower Systems at
service@cyberpower-eu.com
Turn the UPS off. Wait 10 seconds and
then turn the UPS on.
The unit must be connected to a
220-240V 50/60Hz outlet.
Contact CyberPower Systems at
service@cyberpower-eu.com
Contact CyberPower Systems at
service@cyberpower-eu.com
Turn the UPS off and unplug at least one
piece connected equipment. Unplug the
power cord of the UPS then remove the
fuse compartment beneath the power inlet
of the UPS and replace the blown fuse
with a spare one. Lock the compartment
back to the UPS. Connect power cord
then turn the UPS on. Make sure that your
spare fuse meets the specification.
Allow the unit to recharge for at least 4
hours.
Contact CyberPower Systems at
service@cyberpower-eu.com
Connect the serial/USB cable to the UPS
unit and an open serial port on the back
of the computer. You must use the cable
that came with the unit.
Try another serial/USB port of your
computer.
The unit is not providing
battery power.
The serial cable is not the
cable that was provided with
the unit.
TECHNICAL SPECIFICATIONS
Model
Value 400E
Capacity (VA)
400VA
Capacity (Watts)
240W
Input
Input Voltage Range
Frequency Range
Output
On Battery Output
Voltage
On Battery Output
Frequency
Overload Protection
On Utility: Fuse, On Battery: Internal Current Limiting
Physical
Total # of UPS
Receptacles
Maximum Dimensions
Weight
4.2 Kgs / 9.3 Lbs
Battery
Sealed Maintenance
12V / 4.5Ah x1
Free Lead Acid Battery
Typical Recharge Time
Warning Diagnostics
Indicators
Audible Alarms
Environmental
Operating Temperature
Operating Relative
Humidity
Communication
®
1. PowerPanel
Personal Edition
Software (for USB
Port)
Windows 98/ME/2000/NT/XP/Server 2003/Vista
®
2. PowerPanel
Software (for Serial
Port)
Management
Auto-Charger
Auto-Restart
USB
DEFINITIONS FOR ILLUMINATED LED INDICATORS
LED
Alarm
Fuse
On
Off
Normal
Normal
Two
Flash
Normal
Utility Failure - The UPS is providing battery power to outlets.
Beeps
Rapid
Utility Failure - The UPS is providing battery power. The
Flash
Normal
Beeps
rapid beeps indicate the battery will run out of power shortly.
Overload - Occurs when connected equipment exceeds the
Long
Normal/
rating of the unit. Turn the UPS off and unplug at least one
On/Flash
Beep
Blown
piece of equipment from the UPS. Check the fuse and do the
replacement if necessary. Turn the UPS on.
For more information, visit eu.cyberpowersystems.com or contact
CyberPower Systems B.V.
Flight Forum 3545 5657DW Eindhoven The Netherlands
Tel: +31 40 2348170, E-MAIL: sales@cyberpower-eu.com
CyberPower Systems Inc. (USA) 4241 12th Avenue East Suite 400 Shakopee, MN 55379, U.S.A.
Tel: +1 952 4039500, Fax: +1 952 4030009, E-MAIL: sales@cyberpowersystems.com
Entire contents copyright ©2004 CyberPower Systems B.V., All rights reserved. Reproduction in whole
or in part without permission is prohibited. PowerPanel
CyberPower Systems (USA) Inc.
CyberPower warrants to you, the original purchaser, that CyberPower UPS will be free from defects in
design, assembly, materials and workmanship for two years ( battery is only one year) from the date of
original purchase. Any warranty services, please contact your local dealers or distributors.
Shutdown your computer and turn the
UPS off. Wait 10 seconds and turn the
UPS back on. This should reset the unit.
You must use the cable included with the
unit for the software.
Value 600E
Value 800E
600VA
800VA
360W
480W
165-270Vac
45~65 Hz (Auto Sensing)
Simulated Sine Wave at 230Vac +/-10%
50/60 Hz
(3) IEC 320 C13
32cm(L)*10cm(W)*14cm(H)
5.3 Kgs / 11.7 Lbs
6.1 Kgs / 13.4 Lbs
12V / 7Ah x1
12V / 8.5Ah x1
8 Hours
Power On / Using Battery
On Battery, Low Battery, Overload
+32°F to 95°F ( 0°C to 35°C )
0 to 95% NON-CONDENSING
Yes
Yes
Yes
Condition
®
®
and PowerPanel
Plus are trademarks of