Designer Series Gas Fireplaces

REaR waLL VENT INSTaLLaTIoN

When installed as a rear vent unit this appliance may be vented directly to a termination located on
the rear wall behind the appliance
The maximum horizontal distance between the rear of the appliance and the outside face of the
rear wall is 0" (508 m). Figure 17
Only one 45° elbow is allowed in these installations.
0"
(508 mm)
Figure 17 -
Rear Vent Application, Maximum
Horizontal Distance
DVR584-600
1. Locate and cut the vent opening in the wall. For
combustible walls first frame in opening.
Rear vent no elbows
Combustible walls: Cut a 11Z\x"H x 9Z\x" W (9 x
2/99 djt
41 mm) hole through the exterior wall and frame as
shown. Figure 18
Noncombustible walls: Hole opening should be 7Z\x"
(190 mm) in diameter.
. Rigid vent pipes and fittings have special twist-lock
connections. Assemble the desired combination of
pipe and elbows to the appliance adaptor with pipe
seams oriented towards the wall or floor.
Twist-lock Procedure: The female ends of the pipes
and fittings have three locking lugs (indentations).
These lugs will slide straight into matching slots on
the male end of adjacent pipes and fittings. Push the
pipe sections together and twist one section clockwise
approximately one-quarter turn until the sections are
fully locked. Figure 19
3. Attach vent pipe assembly to the fireplace. Set fire-
place in front of its permanent location to insure mini-
mum clearances. Mark the wall for a 11Z\x"H x 9Z\x"W
(9 x 41 mm) rectangle hole (for noncombustible
material such as masonry block or concrete, a 7Z\x"
[190 mm] diameter hole is acceptable). Figure 18.
The center of the hole should line up with the center
line of the horizontal rigid vent pipe end. Be sure to
allow for minimum rise. Cut a 11Z\x"x9Z\x" rectangle hole
through combustible exterior wall (7Z\x" diameter hole
if noncombustible). Frame as necessary. Allow 1/4"
minimum rise per foot. Figure 18
16
Top View Flat
Installation
FP1953
rigid pipe
9Z\x"
(41 mm)
11Z\x"
(9 mm)
7Z\x"
(190 mm)
Figure 18 -
Vent Opening Requirements
FP1954
wall framing
Female Locking
Lugs
Male Slots
FP1953
Figure 19 -
Rigid Vent Pipe Connections
VENTING INSTaLLaTIoN
NoTE: Horizontal runs of vent must
be supported every three (3) feet
(914 mm). Use wall straps for this
purpose.
FP1954
53D0419